Plan Review Notes For Permit 19040094 |
Permit Number |
19040094 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-08-11 07:03:43 | 1) INDICATE ON THE PLANS IF THE NEW STACKABLE | | WASHER/DRYER IS CONNECTING TO EXISTING WATER AND DRAIN | | LINES. IF NEW WATER AND DRAIN LINES ARE BEING | | INSTALLED, SUBMIT A SANITARY AND WATER RISER DIAGRAM | | THAT CLEARLY REFLECTS THE SCOPE OF THE PLUMBING WORK TO | | BE DONE.WPB AMEND. TO FBC SEC. 107.2.1, 107.3..5.1.3. | | 2) IF A NEW DRAIN LINE IS BEING INSTALLED FOR THE | | WASHER, IT SHALL BE A MINIMUM OF 3 INCHES IN DIAMETER | | UP TO THE TRAP FOR THE WASHER STANDPIPE.FBC-PLUMBING | | SEC.406..2. | | 3) THE WATER HEATERS SHALL BE EQUIPPED WITH PROVISIONS | | FOR THERMAL EXPANSION PER FBC-PLUMBING SEC.607.3. | | 4) THE WATER HEATERS SHALL BE INSTALLED WITH A HEATER | | PAN AND PAN DRAIN IN ACCORDANCE WITH FBC-PLUMBING | | SEC.504.6. | | 5) THE SSHUTOFF VALVES FOR THE STACKABLE WASHER/DRYER | | SHALL BE PROVIDED WITH ACCESS PER FBC-PLUMBING | | SEC.606.3. | | 6) PLANS SHALL BEAR THE SIGNATURE AND SEAL OF THE | | DESIGN PROFESSIONAL. FL. ADMIN. CODE RULE 61G1-16.001. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|