Plan Review Notes
Plan Review Notes For Permit 19040094
Permit Number 19040094
Review Stop E
Sequence Number 2
Notes
Date Text
2019-12-22 10:22:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 BE ADVISED THAT THE CURRENT PLAN IS SUBSTANTIALLY
 LACKING OF INFORMATION. THEREFORE, THERE MAY BE
 ADDITIONAL COMMENTS FOR SECOND REVIEW THAT ARE NOT
 ADDRESSED IN THIS REVIEW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED, BUT FURTHER CORRECTIONS NEEDED BASED ON
 SUBMISSION, SEE NEW COMMENTS BELOW.
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION
 IS NOT ACCURATE AND DOES NOT INCLUDE ALL EQUIPMENT.
 FURTHERMORE, THE AMOUNT OF VA SPECIFIED FOR MANY OF THE
 ITEMS DOES NOT CORRESPOND TO KNOW VALUES. PROVIDE
 CORRECTIONS AND MANUFACTURERES SPECIFICATION FOR
 EQUIPMENT.)
 4. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 210.20, 215.5, 408.4 (ONLY ONE PANEL IS SHOWN
 IN RISER DIAGRAM, BUT IS IS NOT POSSIBLE TO HAVE THE
 CIRCUITS FOR ALL THREE UNITS IN THIS ONE PANEL.
 ADDITIONALLY, EACH OCCUPANT SHALL HAVE READY ACCESS TO
 ALL OVERCURRENT DEVICES PROTECTING THE CONDUCTORS
 SUPPLYING THAT OCCUPANCY. PROVIDE CORRECTION. NEC
 240.24(B))
 5. PLAN SEEMS TO INDICATE THERE WILL BE A NEW
 ELECTRICAL SERVICE. PROVIDE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. PROVIDE
 AIC RATING OF ALL ELECTRICAL SERVICE EQUIPMENT AND
 PANELS. NEC 110.3, 110.9, 110.10 (PLAN STATED NEW METER
 AND NEW PANEL. PROVIDE AS PREVIOUSLY REQUESTED.)
 6. CORRECTED.
  
 NEW COMMENTS:
  
 7. PROVIDE ACCURATE RISER DIAGRAM THAT IS CODE
 COMPLIANT, SHOWING ALL DETAILS OF SERVICE EQUIPMENT,
 UNDERGROUND OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES
 FOR SERVICE AND FEED TO ANY SUB-PANEL(S). SHOW GEC SIZE
 AND SYSTEM, SHOW INTERSYSTEM BONDING TERMINATION POINT.
 THE RISER DIAGRAM SHOULD REFLECT THE REQUIRED PANEL TO
 EACH TENANT SPACE. ONLY ONE SERVICE IS PERMITTED BASED
 ON LOAD, BUT ADDITIONAL METERS FOR EACH UNIT ARE
 PERMITTED IF SO DESIRED. NEC 215.5, 230.2, 250.50,
 250.94, 408.30
 8. SHOW LOCATION OF ELECTRICAL SERVICE AND ANY
 ELECTRICAL PANELS ON PLAN. WPB FBC 107.2.1
 9. A MINIMUM OF TWO SMALL APPLIANCE BRANCH CIRCUITS ARE
 REQUIRED FOR RECEPTACLE OUTLETS THAT FEED THE KICHEN
 COUNTER SPACE IN EACH UNIT. PROVIDE CORRECTION. NEC
 210.11, 210.52
 10. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S) IN
 EACH UNIT. SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52
 11. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 12. AFCI PROTECTION AS SHOWN IN NOTE 2 IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 13. NOTE 6 QUOTES THE 2011 NEC FOR COMPLIANCE OF TAMPER
 RESISTANT RECEPTACLES. THE 2011 NEC IS NOT THE CURRENT
 CODE. THIS NOTE ALSO QUOTES THE WRONG CODE SECTION,
 406.10, WHICH DOES NOT APPLY. PROVIDE CORRECTIONS. FBC
 PREFACE. NEC 406.12
 14. NOTES 3, 4, AND 5 SPECIFY SMOKE ALARMS, BUT NONE
 ARE SHOWN ON PLAN. PROVIDE SMOKE/CO ALARMS IN EACH
 LOCATION REQUIRED PER CODE TO CONFIRM COMPLIANCE. FBC
 RE R314.3, R315.1; WPB FBC 107.2.1
 15. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901
 16. PANEL SCHEDULE SHOWS A GARAGE DOOR CIRCUIT, AND A
 CIRCUIT FOR LIFT STATION. THESE ARE NOT SHOWN ON PLAN
 ANYWHERE. PROVIDE CLARIFICATION AND/OR CORRECTIONS AS
 NEEDED. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  