2019-12-22 10:22:51 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| BE ADVISED THAT THE CURRENT PLAN IS SUBSTANTIALLY |
| LACKING OF INFORMATION. THEREFORE, THERE MAY BE |
| ADDITIONAL COMMENTS FOR SECOND REVIEW THAT ARE NOT |
| ADDRESSED IN THIS REVIEW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. CORRECTED. |
| 2. CORRECTED, BUT FURTHER CORRECTIONS NEEDED BASED ON |
| SUBMISSION, SEE NEW COMMENTS BELOW. |
| 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION |
| IS NOT ACCURATE AND DOES NOT INCLUDE ALL EQUIPMENT. |
| FURTHERMORE, THE AMOUNT OF VA SPECIFIED FOR MANY OF THE |
| ITEMS DOES NOT CORRESPOND TO KNOW VALUES. PROVIDE |
| CORRECTIONS AND MANUFACTURERES SPECIFICATION FOR |
| EQUIPMENT.) |
| 4. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY |
| NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| 210.19, 210.20, 215.5, 408.4 (ONLY ONE PANEL IS SHOWN |
| IN RISER DIAGRAM, BUT IS IS NOT POSSIBLE TO HAVE THE |
| CIRCUITS FOR ALL THREE UNITS IN THIS ONE PANEL. |
| ADDITIONALLY, EACH OCCUPANT SHALL HAVE READY ACCESS TO |
| ALL OVERCURRENT DEVICES PROTECTING THE CONDUCTORS |
| SUPPLYING THAT OCCUPANCY. PROVIDE CORRECTION. NEC |
| 240.24(B)) |
| 5. PLAN SEEMS TO INDICATE THERE WILL BE A NEW |
| ELECTRICAL SERVICE. PROVIDE AVAILABLE SHORT CIRCUIT |
| CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE |
| POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT |
| CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC |
| RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. PROVIDE |
| AIC RATING OF ALL ELECTRICAL SERVICE EQUIPMENT AND |
| PANELS. NEC 110.3, 110.9, 110.10 (PLAN STATED NEW METER |
| AND NEW PANEL. PROVIDE AS PREVIOUSLY REQUESTED.) |
| 6. CORRECTED. |
| |
| NEW COMMENTS: |
| |
| 7. PROVIDE ACCURATE RISER DIAGRAM THAT IS CODE |
| COMPLIANT, SHOWING ALL DETAILS OF SERVICE EQUIPMENT, |
| UNDERGROUND OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES |
| FOR SERVICE AND FEED TO ANY SUB-PANEL(S). SHOW GEC SIZE |
| AND SYSTEM, SHOW INTERSYSTEM BONDING TERMINATION POINT. |
| THE RISER DIAGRAM SHOULD REFLECT THE REQUIRED PANEL TO |
| EACH TENANT SPACE. ONLY ONE SERVICE IS PERMITTED BASED |
| ON LOAD, BUT ADDITIONAL METERS FOR EACH UNIT ARE |
| PERMITTED IF SO DESIRED. NEC 215.5, 230.2, 250.50, |
| 250.94, 408.30 |
| 8. SHOW LOCATION OF ELECTRICAL SERVICE AND ANY |
| ELECTRICAL PANELS ON PLAN. WPB FBC 107.2.1 |
| 9. A MINIMUM OF TWO SMALL APPLIANCE BRANCH CIRCUITS ARE |
| REQUIRED FOR RECEPTACLE OUTLETS THAT FEED THE KICHEN |
| COUNTER SPACE IN EACH UNIT. PROVIDE CORRECTION. NEC |
| 210.11, 210.52 |
| 10. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S) IN |
| EACH UNIT. SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52 |
| 11. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| EQUIPMENT PER CODE. NEC 210.63 |
| 12. AFCI PROTECTION AS SHOWN IN NOTE 2 IS NOT CODE |
| COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| 13. NOTE 6 QUOTES THE 2011 NEC FOR COMPLIANCE OF TAMPER |
| RESISTANT RECEPTACLES. THE 2011 NEC IS NOT THE CURRENT |
| CODE. THIS NOTE ALSO QUOTES THE WRONG CODE SECTION, |
| 406.10, WHICH DOES NOT APPLY. PROVIDE CORRECTIONS. FBC |
| PREFACE. NEC 406.12 |
| 14. NOTES 3, 4, AND 5 SPECIFY SMOKE ALARMS, BUT NONE |
| ARE SHOWN ON PLAN. PROVIDE SMOKE/CO ALARMS IN EACH |
| LOCATION REQUIRED PER CODE TO CONFIRM COMPLIANCE. FBC |
| RE R314.3, R315.1; WPB FBC 107.2.1 |
| 15. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS |
| FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS |
| SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE |
| IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A |
| RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES |
| NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION. |
| NEC 210.52(C)(1); FBC RE E3901 |
| 16. PANEL SCHEDULE SHOWS A GARAGE DOOR CIRCUIT, AND A |
| CIRCUIT FOR LIFT STATION. THESE ARE NOT SHOWN ON PLAN |
| ANYWHERE. PROVIDE CLARIFICATION AND/OR CORRECTIONS AS |
| NEEDED. WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |