Plan Review Notes
Plan Review Notes For Permit 19040094
Permit Number 19040094
Review Stop B
Sequence Number 2
Notes
Date Text
2019-12-17 14:54:212017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040094
 ADD: 905 9TH ST. / PCN: 74-43-43-16-01-140-0130
 CONT: SUNRISE CITY
 TEL: 561-350-5866
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. DEC. 17/2019
 ACTION: DENIED
  
 1-6) SEMI- COMPLIED. THIS IS THE 1ST REVIEW WITH A SET
 OF PLANS THAT ARE ORIGINAL SIGNED AND SEALED PLANS.
 THE SHEET A-0.3 INDICATES BETWEEN THE R2 OCCUPANCIES
 THERE IS A ONE HOUR FIRE RATED WALL ALL THE WAY TO THE
 ROOF DECK. THE PLANS ARE SILENT AS TO WHAT MATERIALS
 ARE GOING TO MAKE UP THE ONE HOUR FIRE RATING. SHEET
 A-3.1 INDICATES THE TENANT SEPARATION WALLS WITH A WALL
 TYPE IDENTIFICATION TAG, (F) 1 5/8 METAL FURRING.
 PLEASE PROVIDE EITHER A UL WALL LISTING AND SHOW THE
 WALL COMPONENTS OR GYPSUM ASSOCIATION WALL LISTING AND
 THEIR COMPONENTS AND HOURLY FIRE RATING. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTION 420.2 SEPARATION
 WALLS/ FIRE PARTITIONS. THE COMMON WALL BETWEEN THE R-2
 UNITS NEEDS TO SHOW COMPLIANCE WITH THE 2017 FBC-B
 SECTION 708, FIRE PARTITIONS. PLEASE SHOW COMPLIANCE
 WITH 2017 FBC-B SECTION:
 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE
 TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW
 TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB
 OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL
 BE SECURELY ATTACHED THERETO.
  
 6) THERE SEEMS TO BE A DISCREPANCY WITHIN THE SET OF
 PLANS. SHEET A-0.4 THE DEMO PLAN STATES ALL EXTERIOR
 WINDOWS AND DOORS TO REMAIN. WHEREAS SHEET A-3.2 NOTE #
 2 IN THE LOWER LEFT HAND CORNER OF THE SHEET INDICATES
 THE EXISTING WINDOWS AND DOORS ARE TO BE REPLACED.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED,
 DISCREPANCY.
  
 6A) THE WIND DESIGN CRITERIA HAS BEEN PROVIDED AND
 ASSOCIATED VULT PRESSURES. PLEASE PROVIDE THE
 ASSOCIATED PRESSURES IN VASD SINCE THE PRODUCT
 APPROVALS HAVE ALL BEEN TESTED IN VASD AND RECORDED
 RESULT ARE IN VASD. 1609.3.1 WIND SPEED CONVERSION VULT
 TO VASD.
  
 6B) IF WINDOWS AND DOORS ARE TO BE REPLACED PLEASE SHOW
 COMPLIANCE WITH: 2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (E) SHUTTERS
  
 6C) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6D) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  