2019-04-18 10:39:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PLUMBING REVIEW CONDUCTED IN ACCORDANCE WITH WPB FBC
 107.3.5.1.3
 2. PER WPB FBC 107.2.1, PROVIDE THE BUILDING
 CLASSIFICATION/OCCUPANCY AS PRESCRIBED IN FBC CHAPTER 3
 AND OCCUPANT LOAD CALCULATIONS IN ACCORDANCE WITH FBC
 1004 AND 1005.
 3. CONTINGENT UPON THE DETERMINATION OF THE BUILDING
 CLASSIFICATION/OCCUPANCY, CLOTHES WASHER FACILITIES
 WILL BE REQUIRED IN ACCORDANCE WITH FBC PL TABLE 403.1.
 4. PER WPB FBC 107.2.1, PROVIDE DEDICATED PLUMBING
 FLOOR PLAN NOTING A COMPLETE SCOPE OF WORK; INDICATE ON
 THE PLAN PLUMBING FIXTURES, WATER HEATERS AND
 APPLIANCES TO BE REPLACED. ADDITIONALLY, INDICATE ON
 THE PLANS TUB/SHOWER VALVE REPLACEMENT. PROVIDE NOTE ON
 THE PLAN CONFIRMING THAT ROUGH/TOP OUT WORK WILL BE
 LIMITED TO IN WALL REPLACEMENT OF TUB SHOWER VALVES AND
 PROVISION FOR WATER HAMMER ARRESTORS FOR CLOTHES
 WASHERS (SEE NOTE 2); IF THERE IS TO BE MORE EXTENSIVE
 ROUGH/TOP OUT WORK, THEN IT SHALL BE INDICATED ON THE
 PLANS. THE PLAN SHALL BE CLEAR AND LEGIBLE AND COMPLY
 WITH WPB FBC 107.2.1.3.
 5. THE PLAN SHALL BE STAMPED/SEALED AND SIGNED BY
 DESIGNER OF RECORD IN ACCORDANCE WITH FS 471 AND FAC
 61G15.
 6. PER WPB FBC 107.2.1, PROVIDE THE NOTE ?INDIVIDUAL
 SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE PER FBC PL 424.3.?
 7. PROVIDE WATER HEATER SPEC WITH CAPACITY AND
 ELECTRICAL CHARACTERISTICS. ELECTRICAL CHARACTERISTICS
 SHALL MATCH ELECTRICAL PLANS.
 8. PER WPB FBC 107.2.1, PROVIDE THE NOTE ?WATER HEATER
 INSTALLATION SHALL COMPLY WITH FBC PL CHAPTER 5 AND FBC
 PL 607.3.?
 9. PER WPB FBC 107.2.1, PROVIDE THE NOTE ?A
 WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010 PER BY FBC PL 604.9.?
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715