Date |
Text |
2019-04-18 10:39:48 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL |
| MANUAL |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| 1. PLUMBING REVIEW CONDUCTED IN ACCORDANCE WITH WPB FBC |
| 107.3.5.1.3 |
| 2. PER WPB FBC 107.2.1, PROVIDE THE BUILDING |
| CLASSIFICATION/OCCUPANCY AS PRESCRIBED IN FBC CHAPTER 3 |
| AND OCCUPANT LOAD CALCULATIONS IN ACCORDANCE WITH FBC |
| 1004 AND 1005. |
| 3. CONTINGENT UPON THE DETERMINATION OF THE BUILDING |
| CLASSIFICATION/OCCUPANCY, CLOTHES WASHER FACILITIES |
| WILL BE REQUIRED IN ACCORDANCE WITH FBC PL TABLE 403.1. |
| 4. PER WPB FBC 107.2.1, PROVIDE DEDICATED PLUMBING |
| FLOOR PLAN NOTING A COMPLETE SCOPE OF WORK; INDICATE ON |
| THE PLAN PLUMBING FIXTURES, WATER HEATERS AND |
| APPLIANCES TO BE REPLACED. ADDITIONALLY, INDICATE ON |
| THE PLANS TUB/SHOWER VALVE REPLACEMENT. PROVIDE NOTE ON |
| THE PLAN CONFIRMING THAT ROUGH/TOP OUT WORK WILL BE |
| LIMITED TO IN WALL REPLACEMENT OF TUB SHOWER VALVES AND |
| PROVISION FOR WATER HAMMER ARRESTORS FOR CLOTHES |
| WASHERS (SEE NOTE 2); IF THERE IS TO BE MORE EXTENSIVE |
| ROUGH/TOP OUT WORK, THEN IT SHALL BE INDICATED ON THE |
| PLANS. THE PLAN SHALL BE CLEAR AND LEGIBLE AND COMPLY |
| WITH WPB FBC 107.2.1.3. |
| 5. THE PLAN SHALL BE STAMPED/SEALED AND SIGNED BY |
| DESIGNER OF RECORD IN ACCORDANCE WITH FS 471 AND FAC |
| 61G15. |
| 6. PER WPB FBC 107.2.1, PROVIDE THE NOTE ?INDIVIDUAL |
| SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE |
| BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION |
| BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA |
| B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE |
| INSTALLED AT THE POINT OF USE PER FBC PL 424.3.? |
| 7. PROVIDE WATER HEATER SPEC WITH CAPACITY AND |
| ELECTRICAL CHARACTERISTICS. ELECTRICAL CHARACTERISTICS |
| SHALL MATCH ELECTRICAL PLANS. |
| 8. PER WPB FBC 107.2.1, PROVIDE THE NOTE ?WATER HEATER |
| INSTALLATION SHALL COMPLY WITH FBC PL CHAPTER 5 AND FBC |
| PL 607.3.? |
| 9. PER WPB FBC 107.2.1, PROVIDE THE NOTE ?A |
| WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE |
| QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER |
| ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS |
| SHALL CONFORM TO ASSE 1010 PER BY FBC PL 604.9.? |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN |
| ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |