2019-04-16 07:55:37 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE SANITARY ISOMETRIC HAS THE FOLLOWING CODE |
| VIOLATIONS. |
| A) THE FIXTURE BRANCH FOR THE WC SHALL BE MIN OF 3" PER |
| FBC PL 420.4 |
| B) THE FIXTURE BRANCHES FOR ALL THE FIXTURES IN THE |
| BATHROOM GROUP SHALL CONNECT TO THE HORIZONTAL WET VENT |
| INDIVIDUALLY THEY APPEAR TO BE CONNECTED TO THE |
| VERTICAL VENT FOR THE LAVATORY. PER FBC PL 912.1.1 |
| C) THE KITCHEN SINK SHALL NOT DISCHARGE TO THE BATHROOM |
| GROUP IT SHALL CONNECT TO BUILDING DRAIN DOWN STREAM |
| FROM ALL THE BATHROOM GROUP. PER FBC PL 912.1.1 |
| D) THE WASHING MACHINE IS MISSING FROM THE SANITARY |
| ISOMETRIC. PER WPB AMEND TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |