Plan Review Notes
Plan Review Notes For Permit 19031380
Permit Number 19031380
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-16 07:55:371ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SANITARY ISOMETRIC HAS THE FOLLOWING CODE
 VIOLATIONS.
 A) THE FIXTURE BRANCH FOR THE WC SHALL BE MIN OF 3" PER
 FBC PL 420.4
 B) THE FIXTURE BRANCHES FOR ALL THE FIXTURES IN THE
 BATHROOM GROUP SHALL CONNECT TO THE HORIZONTAL WET VENT
 INDIVIDUALLY THEY APPEAR TO BE CONNECTED TO THE
 VERTICAL VENT FOR THE LAVATORY. PER FBC PL 912.1.1
 C) THE KITCHEN SINK SHALL NOT DISCHARGE TO THE BATHROOM
 GROUP IT SHALL CONNECT TO BUILDING DRAIN DOWN STREAM
 FROM ALL THE BATHROOM GROUP. PER FBC PL 912.1.1
 D) THE WASHING MACHINE IS MISSING FROM THE SANITARY
 ISOMETRIC. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  