2019-04-20 08:16:15 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. SHOW CONDUCTOR SIZE FROM RISER TO METER-CAN FBC |
| 107.2.1 |
| |
| 2. SHOW CONDUCTOR SIZE FROM METER-CAN TO MAIN-BREAKER |
| PANEL. FBC 107.2.1 |
| |
| 3. PROVIDE ACCUATE LOAD CALCULATION. OCP FOR COOKTOP IS |
| SHOWN AS 40AMPS BUT ONLY 1200 WATTS SHOWN IN LOAD |
| CALCULATION. FBC 107.2.1 NEC 220 |
| |
| 4. SHOW CIRCUITS BEING FED FROM MAIN-BREAKER PANEL (IF |
| ANY). FBC 107.2.1 |
| |
| 5. SHOW AFCI PROTECTION FOR KITCHEN LIGHTING AND |
| KITCHEN COUNTERTOP RECEPTACLES. NEC 210.12 |
| |
| 6.SHOW AFCI PROTECTION FOR DISHWASHER AND DISPOSAL. NEC |
| 210.12 |
| |
| 7. SHOW GFCI PROTECTION FOR DISHWASHER. NEC 210.8D |
| |
| 8. RECEPTACLE REQUIRED ON ISLAND. RECEPTACLE SHOWN IS |
| NOT CODE COMPLIANT. OVERHANG OF COUNTERTOP IS MORE THAN |
| 6''. PLEASE SEE NEC 210.52C5 (EXCEPTION TO #5) |
| |
| 9. SMOKE ALARM REQUIRED OUTSIDE OF NEW BEDROOM. FBC |
| 314&315 |
| |
| 10. SHOW AFCI PROTECTION FOR RECEPTACLES IN |
| LAUNDRY/UTILITY ROOM. NEC 210.12 |
| |
| 11. NOTE ON PLANS STATES 50% OF ALL LIGHTING WILL BE |
| ENERGY EFFICIENT. PLEASE SEE FBC EC R404.1. MINIMUM IS |
| 75% |
| |
| PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |