Plan Review Notes
Plan Review Notes For Permit 19031380
Permit Number 19031380
Review Stop E
Sequence Number 1
Notes
Date Text
2019-04-20 08:16:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHOW CONDUCTOR SIZE FROM RISER TO METER-CAN FBC
 107.2.1
  
 2. SHOW CONDUCTOR SIZE FROM METER-CAN TO MAIN-BREAKER
 PANEL. FBC 107.2.1
  
 3. PROVIDE ACCUATE LOAD CALCULATION. OCP FOR COOKTOP IS
 SHOWN AS 40AMPS BUT ONLY 1200 WATTS SHOWN IN LOAD
 CALCULATION. FBC 107.2.1 NEC 220
  
 4. SHOW CIRCUITS BEING FED FROM MAIN-BREAKER PANEL (IF
 ANY). FBC 107.2.1
  
 5. SHOW AFCI PROTECTION FOR KITCHEN LIGHTING AND
 KITCHEN COUNTERTOP RECEPTACLES. NEC 210.12
  
 6.SHOW AFCI PROTECTION FOR DISHWASHER AND DISPOSAL. NEC
 210.12
  
 7. SHOW GFCI PROTECTION FOR DISHWASHER. NEC 210.8D
  
 8. RECEPTACLE REQUIRED ON ISLAND. RECEPTACLE SHOWN IS
 NOT CODE COMPLIANT. OVERHANG OF COUNTERTOP IS MORE THAN
 6''. PLEASE SEE NEC 210.52C5 (EXCEPTION TO #5)
  
 9. SMOKE ALARM REQUIRED OUTSIDE OF NEW BEDROOM. FBC
 314&315
  
 10. SHOW AFCI PROTECTION FOR RECEPTACLES IN
 LAUNDRY/UTILITY ROOM. NEC 210.12
  
 11. NOTE ON PLANS STATES 50% OF ALL LIGHTING WILL BE
 ENERGY EFFICIENT. PLEASE SEE FBC EC R404.1. MINIMUM IS
 75%
  
 PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  