Plan Review Notes
Plan Review Notes For Permit 19031364
Permit Number 19031364
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-05 08:20:07PLUMBING 1ST REVIEW**DENIED**
  
 1) SHT. 1 OF 2 SHOWS ELECTRIC HEAT PUMP PAD BUT UNDER
 DETAILS THE PLAN CALLS OUT FOR A 400,000 BTU GAS
 HEATER. YOU ALSO DID NOT SUBMIT ANY POOL HEATER SPEC,
 MANUFACTURE INSTALLATION MANAUL. FBC 107.2.1, FBC
 107.3.5
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  