Plan Review Notes For Permit 19031322 |
Permit Number |
19031322 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-08-02 13:23:23 | 1) THERE ARE TWO GAS DRAWINGS IN THIS SUBMITTAL. ONE | | SHOWS A 15 KW GENERATOR AND THE OTHER SHOWS A 22 KW | | GENERATOR. WHAT ARE YOU INSTALLING? YOU SHOW RWO | | DIFFERENT GENERATORS WITH THE SAME BTU LOAD OF 281,000 | | WHICH DOES NOT THE MATCH THE BTU LOAD IN THE | | MANUFACTURER'S INSTALLATION MANUAL. SUBMIT TWO COPIES | | OF A GAS DRAWING THE CORRECT SIZE GENERATOR AND BTU | | LOAD. WPB AMEND. TO FBC SEC. 107.2.1. | | 2) A UNION IS REQD. WITHIN ONE FOOT UPSTREAM OR | | DOWNSTREAM OF EACH REGULATOR. SHOW THIS ON THE PLAN. | | |
|