Plan Review Notes For Permit 19031322 |
Permit Number |
19031322 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-05-07 10:52:06 | GAS 2ND REVIEW**DENIED** I WOULD RECOMMEND COMMING IN | | FOR A REVIEW BEFORE RESUBMITTING. | | | | PLAN'S SUBMITTED ARE SO DEFICIENT A THOROUGH PLAN | | REVIEW COULD NOT BE PERFORMED AT THIS TIME. THE SURVEY | | AND ELC PLAN CALLS FOR A 15KW GENERATOR. INSTALLATION | | MANUAL PROVIDE LIST 6KW, 12KW, 13KW FOR NAT GAS. BOTH | | GAS RISERS CALL OUT 22KW. EACH OF THE GAS RISERS CALL | | OUT DIFFERENT BTU'S OF THE NEW GENERATOR. NO | | INSTALLATION MANUAL FOR A 22KW WAS PROVIDED | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | 561-248-2703 | | [email protected] | | [email protected] | | | | | | |
|