2019-05-07 10:52:06GAS 2ND REVIEW**DENIED** I WOULD RECOMMEND COMMING IN
 FOR A REVIEW BEFORE RESUBMITTING.
  
 PLAN'S SUBMITTED ARE SO DEFICIENT A THOROUGH PLAN
 REVIEW COULD NOT BE PERFORMED AT THIS TIME. THE SURVEY
 AND ELC PLAN CALLS FOR A 15KW GENERATOR. INSTALLATION
 MANUAL PROVIDE LIST 6KW, 12KW, 13KW FOR NAT GAS. BOTH
 GAS RISERS CALL OUT 22KW. EACH OF THE GAS RISERS CALL
 OUT DIFFERENT BTU'S OF THE NEW GENERATOR. NO
 INSTALLATION MANUAL FOR A 22KW WAS PROVIDED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  