2019-05-01 18:43:28 | BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- PROPOSED FLOOR PLAN ON SHEET A-2: IT LOOKS LIKE ONE |
| OF THE NEW DOUBLE DOORS ON THE RIGHT HAND SIDE IS |
| ENCROACHING MORE THAN ONE HALF OF THE WIDTH OF |
| CORRIDOR. REVISE AS REQUIRED. SEC. 1005.7.1 |
| FBC-BUILDING. |
| |
| 2- PROVIDE COMPLETE DIMENSIONS FOR NEW TOILET |
| COMPARTMENTS SHOWN ON ENLARGED FLOOR PLAN ON SHEET A-3. |
| ONLY DIMENSIONS ON ONE DIRECTION WERE GIVEN. SEC. |
| 604.8.1.1 FBC-ACCESSIBILITY. |
| |
| 3- SHEET A-2: |
| A) PROVIDE DIMENSIONS FOR NEW DOOR "B" SHOWING |
| COMPLIANCE WITH THE MANEUVERING CLEARANCES REQUIRED BY |
| SEC. 404.2.4 FBC-ACCESSIBILITY FOR FRONT APPROACH. |
| |
| B) WALL LEGEND SHOWN ON PROPOSED CEILING PLAN IS NOT |
| CLEAR. THERE ARE TWO DIFFERENT WALL LEGENDS SHOWN ON |
| THIS SIDE OF THE DRAWING. ONE IS SHOWN ON THE TOP LEFT |
| OF PLAN AND THE OTHER ONE IS SHOWN ON THE TOP RIGHT. |
| INFORMATION DOESN'T MATCH WALLS SHOWN ON THE CEILING |
| PLAN. ACCORDING TO PROPOSED FLOOR PLAN, IT LOOKS LIKE |
| THERE ARE NEW FIRE RATED PARTITIONS NOT EXISTING. |
| REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C) REVISE SECTION DETAIL 1/A-3 KEYED ON THE PROPOSED |
| FLOOR PLAN. DETAIL 1 ON SHEET A-3 DOESN'T CORRESPOND TO |
| THE RATED PARTITION. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |