2019-04-04 10:59:39***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING PLAN REVIEW DENIED:
  
 THE PERMIT APPLIED FOR IS FOR AN INTERIOR DEMO. ONLY.
 IN ADDITION TO THE INTERIOR DEMOLITION OF AREA
 IDENTIFIED ON APPLICATION, THE PLANS INCLUDE DEMOLITION
 AND REMODELING OF STRUCTURAL ELEMENTS. THE STRUCTURAL
 WORK SHOULD NOT BE ON THIS PLAN AS APPLIED FOR.
  
 PLEASE EITHER:
 1. ADJUST THE DESCRIPTION OF WORK, ADD SPECIAL
 INSPECTOR AGREEMENT/SPECIAL INSPECTION PLAN, AND ADJUST
 THE VALUATION/PROVIDE VALUATION BREAK DOWN TO INCLUDE
 STRUCTURAL WORK.
 OR
 2. REMOVE STRUCTURAL WORK FROM PLAN AND APPLY FOR
 SEPERATE COMMERCIAL PERMIT FOR STRUCTURAL WORK.