2019-03-28 18:32:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED
  
 1) THE BUILDING IS LOCATED IN EXPOSURE C WITH A 170 MPH
 VULT WINDSPEED. THE MAXIMUM DESIGN PRESSURE FOR THE
 SYSTEM YOU SELECTED IS -60 PSF. THIS IS NOT ADEQUATE AT
 THE CORNER AND PERIMETER AREAS. GENERAL LIMITATION
 NUMBER 7 ON THE NOA, ALLOWS FOR ENHANCED FASTENING IN
 THESE AREAS TO INCREASE UPLIFT PRESSURES. SUBMIT SIGNED
 AND SEALED RAS 117 CALCULATIONS.