Plan Review Notes For Permit 19031255 |
Permit Number |
19031255 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-04-12 13:35:44 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | SERVICE MAIN WENT FROM 200 AMPERES DOWN TO 150 AMPERES | | | | PLEASE SUBMIT A LOAD CALCULATION THAT SUPPORTS THIS | | CHANGE 220.40 |
|