Plan Review Notes
Plan Review Notes For Permit 19031212
Permit Number 19031212
Review Stop E
Sequence Number 2
Notes
Date Text
2019-06-04 06:36:03ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE ON MONUMENT SIGN PLAN QUOTING "600.6A1 EX #2"
 THERE IS NO EXCEPTION #2 TO 600.6A1 AND EXCEPTION #1
 DOESN'T APPLY TO THIS APPLICATION.
  
 2. DISCONNECT FOR MONUMENT SIGN SHOWN ON PLAN DOES NOT
 MEET THE REQUIREMENTS OF 600.6A1. DISCONNECT MUST
 DISCONNECT ALL BRANCH CIRCUITS CONDUCTORS AT THE POINT
 THEY ENTER THE SIGN. WHEN DISCONNECT IS OPEN ALL 120V
 CONDUCTORS IN SIGN MUST BE DISCONNECTED. PLEASE COMPLY.
 NEC 600.6A1
  
 3. DISCONNECT ON SHEET #3 OF PLAN DOES NOT COMPLY WITH
 600.6A1. PLEASE PROVIDE CORRECTION.
  
 4. DISCONNECT ON SHEET #15 OF PLAN DOES NOT COMPLY WITH
 600.6A1. PLEASE PROVIDE CORRECTION.
  
 5. DISCONNECT ON SHEET # 17 OF PLAN DOES NOT COMPLY
 WITH 600.6A1. PLEASE PROVIDE CORRECTION.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  