2019-06-04 06:36:03 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NOTE ON MONUMENT SIGN PLAN QUOTING "600.6A1 EX #2" |
| THERE IS NO EXCEPTION #2 TO 600.6A1 AND EXCEPTION #1 |
| DOESN'T APPLY TO THIS APPLICATION. |
| |
| 2. DISCONNECT FOR MONUMENT SIGN SHOWN ON PLAN DOES NOT |
| MEET THE REQUIREMENTS OF 600.6A1. DISCONNECT MUST |
| DISCONNECT ALL BRANCH CIRCUITS CONDUCTORS AT THE POINT |
| THEY ENTER THE SIGN. WHEN DISCONNECT IS OPEN ALL 120V |
| CONDUCTORS IN SIGN MUST BE DISCONNECTED. PLEASE COMPLY. |
| NEC 600.6A1 |
| |
| 3. DISCONNECT ON SHEET #3 OF PLAN DOES NOT COMPLY WITH |
| 600.6A1. PLEASE PROVIDE CORRECTION. |
| |
| 4. DISCONNECT ON SHEET #15 OF PLAN DOES NOT COMPLY WITH |
| 600.6A1. PLEASE PROVIDE CORRECTION. |
| |
| 5. DISCONNECT ON SHEET # 17 OF PLAN DOES NOT COMPLY |
| WITH 600.6A1. PLEASE PROVIDE CORRECTION. |
| |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |