2019-04-19 06:39:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. EXTERNAL 120V DISCONNECT REQUIRED FOR ALL SIGNS |
| (WALL AND MONUMENT) MUST CONFORM WITH THE REQUIREMENTS |
| OF 600.6A1 NEC. DISCONNECT MUST BE WITHIN SIGHT OF SIGN |
| AND SHUT DOWN BRANCH CIRCUIT CONDUCTORS FEEDING SIGN. |
| PROVIDE CORRECTIONS |
| |
| 2. PROVIDE NOTE ON PLAN FOR STATING ALL EXTERNAL SIGNS |
| WILL BE CONTROLLED BY AN ASTRONOMICAL TIME CLOCK/W |
| BATTERY BACKUP OR BUILDING MANAGMENT SYSTEM TO CONFORM |
| WITH ENERGY CONSERVATION EXTERNAL LIGHTING REQUIREMENTS |
| OF FBC EC 405.2.4 |
| |
| 3. NO WIRING DIAGRAM PROVIDED FOR MONUMENT SIGN. |
| PROVIDE ELECTRICAL PLAN FOR MONUMENT SIGN. SHOW |
| EXTERNAL DISCONNECT REQUIRED BY 600.6A1 AS DESCRIBED IN |
| PLAN REVIEW COMMENT #1. |
| |
| 4. NO WIRING DIAGRAM PROVIDED FOR "ATM" SIGNS. PROVIDE |
| ELECTRICAL PLAN FOR "ATM" SIGNS. SHOW EXTERNAL |
| DISCONNECT REQUIRED BY 600.6A1 AS DESCRIBED IN PLAN |
| REVIEW COMMENT #1. |
| |
| 5. VALUE SEEMS LOW FOR AMOUNT OF WORK SHOWN. PROVIDE |
| CONTRACT INCLUDING ALL MATIERALS AND LABOR. SIGNED BY |
| BOTH CONTRACTOR AND OWNER. |
| |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |