Plan Review Notes
Plan Review Notes For Permit 19031212
Permit Number 19031212
Review Stop E
Sequence Number 1
Notes
Date Text
2019-04-19 06:39:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. EXTERNAL 120V DISCONNECT REQUIRED FOR ALL SIGNS
 (WALL AND MONUMENT) MUST CONFORM WITH THE REQUIREMENTS
 OF 600.6A1 NEC. DISCONNECT MUST BE WITHIN SIGHT OF SIGN
 AND SHUT DOWN BRANCH CIRCUIT CONDUCTORS FEEDING SIGN.
 PROVIDE CORRECTIONS
  
 2. PROVIDE NOTE ON PLAN FOR STATING ALL EXTERNAL SIGNS
 WILL BE CONTROLLED BY AN ASTRONOMICAL TIME CLOCK/W
 BATTERY BACKUP OR BUILDING MANAGMENT SYSTEM TO CONFORM
 WITH ENERGY CONSERVATION EXTERNAL LIGHTING REQUIREMENTS
 OF FBC EC 405.2.4
  
 3. NO WIRING DIAGRAM PROVIDED FOR MONUMENT SIGN.
 PROVIDE ELECTRICAL PLAN FOR MONUMENT SIGN. SHOW
 EXTERNAL DISCONNECT REQUIRED BY 600.6A1 AS DESCRIBED IN
 PLAN REVIEW COMMENT #1.
  
 4. NO WIRING DIAGRAM PROVIDED FOR "ATM" SIGNS. PROVIDE
 ELECTRICAL PLAN FOR "ATM" SIGNS. SHOW EXTERNAL
 DISCONNECT REQUIRED BY 600.6A1 AS DESCRIBED IN PLAN
 REVIEW COMMENT #1.
  
 5. VALUE SEEMS LOW FOR AMOUNT OF WORK SHOWN. PROVIDE
 CONTRACT INCLUDING ALL MATIERALS AND LABOR. SIGNED BY
 BOTH CONTRACTOR AND OWNER.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  