2019-03-29 08:49:11FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PG. E-2 OUTSIDE BEDROOM #3 MISSING SMOKE ALARM/CO
 DETECTOR
  
 PG. E-3 RISER AND PANEL SCHEDULES DON'T MATCH
 PANEL "A" DOES NOT FEED PANEL "C"
 METER MAIN PANEL SCHEDULE NOT SHOWN 2-P 80A FEEDS ?
 LOAD CALCULATION SHOWS LOADS OF 7KW FOR PANEL "C" AND
 10KW FOR PANEL "P" AND THEN DEMANDED AGAIN ON LOAD
 CALC?
 YOU CAN NOT DEMAND LOADS FROM "C" AND "P" TWICE. SHOW
 HOW LOADS ARE CALCULATED TO GET 7K AND 10K
 SHOWS A REFERENCE TO A GENERATOR ON PAGE "GENERATOR IS
 NOT SHOWN" PLEASE INCLUDE IN RISER DIAGRAM.