2019-04-10 10:10:32 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| GAS COMMENTS: |
| |
| 1. PROVIDE DETAIL OF HOW THE END OF THE PIPING WILL BE |
| SECURED SO THAT GAS WILL NOT BE RELEASED INTO SPACE IF |
| SOME ONE ENERGIZES THE 2" LINE A LOCKING VALVE AND CAP |
| IS REQUIRED. PER WPB AMEND TO FBC 107.2.1 AND FBC FG |
| 404.15 |
| 2. PLACE NOTE ON PLAN . CITY OF WEST PALM BEACH PIPING |
| AFFIDAVIT OR MANOMETER TEST DOCUMENT REQUIRED AT |
| JOBSITE FOR FINAL INSPECTION. PER WPB AMEND TO FBC |
| 107.2.1 |
| 3. PLACE NOTE ON THE PLAN THAT PIPING IS FOR FUTURE USE |
| NO APPLIANCES TO BE CONNECTED WITH OUT SEPARATE |
| PERMIT.. PER WPB AMEND TO FBC 107.2.1 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |