Plan Review Notes For Permit 19031191 |
Permit Number |
19031191 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-03-28 13:35:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) SHEET A 1.2 - THERE IS AN INDICATION OF A "NEW | | SHAFT". | | | | WHAT IS THE PURPOSE OF THIS NEW SHAFT? | | | | HOW MANY FLOORS DOES IT CONNECT? | | | | PLEASE PROVIDE DETAILS | | | | | | | | 3) SHEET A 2.2 - THE DOOR TO THE SHAFT IS INDICATED HAS | | HAVING A B RATING. THERE IS NO DEFINITION OF WHAT B IS. | | | | PLEASE PROVIDE DETAILS/DEFINITION. | | | | | | | | | | 4) SHEET A 2.2 - THERE IS NO INDICATION OF THE WIDTH | | DIMENSION BETWEEN THE CORNER OF THE NEW SHAFT WALL AND | | THE EXISTING WALL. | | | | THIS DIMENSION IS REQUIREDTO MEET OR EXCEED THE | | REQUIREMENT FOR EXITING PER NFPA 101, CH 7, MEANS OF | | EGRESS. | | | | PLEASE PROVIDE THE DIMENSION AND CORRECT IR APPLICABLE. | | | | | | | | | | 5) SHEET FP - FIRE SPRINKLER PLANS ARE INDICATED. THESE | | PLANS ARE NOLY REVIEWED FOR INFORMATIONAL PURPOSES. | | | | REVISED FIRE SPRINKLED SHOP DRAWING ARE REQUIRED UNDER | | SEPARATE REVISED PERMIT. | | | | PROVIDE A NOTE OF ACKNOWLEDGEMENT. | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|