Plan Review Notes
Plan Review Notes For Permit 19031173
Permit Number 19031173
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-12 14:41:211ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. S-1 AND S-2 THE SEAL AND SIGNATURE OF THE
 ENGINEER APPEARS TO BE PHOTO COPIED THEY SHALL BE
 ORIGINAL. FAC 61G15-23.003
  
 2. REMOVE STAMP AND SIGNATURE OF PREVIOUS PLUMBING
 EXAMINER SHT. S-2 PER WPB AMEND TO FBC 107.2.1
  
 3. SHT S-2 THE PLUMBING SANITARY RISER IN THE BATHROOM
 GROUP ONLY ONE FIXTURE UP STREAM OF THE WET VENT IS
 ALLOWED THE LAVATORY SHALL CONNECT BETWEEN THE TOILET
 AND TUB. PER FBC RES P3108.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  