2019-04-30 07:54:33 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 19031173 |
| REVIEWED: APRIL 29, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| FBC[R] = FBC RESIDENTIAL |
| |
| 1) 107.5.3 FBC[AMENDED] UPDATE CODE EDITION TO STATE |
| CURRENT VERSION. 2017 FBC 6 TH EDITION. |
| |
| 2) R314.2 FBC[R] WHERE REQUIRED. SMOKE ALARMS SHALL BE |
| PROVIDED IN ACCORDANCE WITH THIS SECTION. |
| R314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. EXCEPTIONS: |
| |
| A. IN EACH SLEEPING ROOM. |
| B.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| VICINITY OF THE BEDROOMS. |
| C. SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET |
| (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A |
| BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS |
| WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY |
| SECTION R314.3. |
| |
| R314.4 FBC[R] INTERCONNECTION. WHERE MORE THAN ONE |
| SMOKE ALARM IS REQUIRED TO BE INSTALLED WITHIN AN |
| INDIVIDUAL DWELLING UNIT IN ACCORDANCE WITH SECTION |
| R314.3, THE ALARM DEVICES SHALL BE INTERCONNECTED IN |
| SUCH A MANNER THAT THE ACTUATION OF ONE ALARM WILL |
| ACTIVATE ALL OF THE ALARMS IN THE INDIVIDUAL DWELLING |
| UNIT. PHYSICAL INTERCONNECTION OF SMOKE ALARMS SHALL |
| NOT BE REQUIRED WHERE LISTED WIRELESS ALARMS ARE |
| INSTALLED AND ALL ALARMS SOUND UPON ACTIVATION OF ONE |
| ALARM. EXCEPTION: INTERCONNECTION OF SMOKE ALARMS IN |
| EXISTING AREAS SHALL NOT BE REQUIRED WHERE ALTERATIONS |
| OR REPAIRS DO NOT RESULT IN REMOVAL OF INTERIOR WALL OR |
| CEILING FINISHES EXPOSING THE STRUCTURE, UNLESS THERE |
| IS AN ATTIC, CRAWL SPACE OR BASEMENT AVAILABLE THAT |
| COULD PROVIDE ACCESS FOR INTERCONNECTION WITHOUT THE |
| REMOVAL OF INTERIOR FINISHES. |
| - |
| |
| ONE-FAMILY AND TWO-FAMILY DWELLINGS AND TOWNHOMES |
| UNDERGOING A REPAIR, OR A LEVEL 1 ALTERATION AS DEFINED |
| IN THE FLORIDA BUILDING CODE, MAY USE SMOKE ALARMS |
| POWERED BY 10-YEAR NONREMOVABLE, NONREPLACEABLE |
| BATTERIES IN LIEU OF RETROFITTING SUCH DWELLING WITH |
| SMOKE ALARMS POWERED BY THE DWELLING?S ELECTRICAL |
| SYSTEM. A BATTERY-POWERED SMOKE ALARM THAT IS NEWLY |
| INSTALLED OR REPLACES AN EXISTING BATTERY-POWERED SMOKE |
| ALARM AS A RESULT OF A LEVEL 1 ALTERATION MUST BE |
| POWERED BY A NONREMOVABLE, NONREPLACEABLE BATTERY THAT |
| POWERS THE ALARM FOR AT LEAST 10 YEARS. THE BATTERY |
| REQUIREMENTS OF THIS SECTION DO NOT APPLY TO A FIRE |
| ALARM, SMOKE DETECTOR, SMOKE ALARM, OR ANCILLARY |
| COMPONENT THAT IS ELECTRONICALLY CONNECTED AS A PART OF |
| A CENTRALLY MONITORED OR SUPERVISED ALARM SYSTEM, THAT |
| USES A LOWPOWER, RADIO FREQUENCY WIRELESS COMMUNICATION |
| SIGNAL; OR THAT CONTAINS MULTIPLE SENSORS, SUCH AS A |
| SMOKE ALARM COMBINED WITH A CARBON MONOXIDE ALARM OR |
| OTHER MULTISENSOR DEVICES, AND IS APPROVED AND LISTED |
| BY A NATIONALLY RECOGNIZED TESTING LABORATORY. |
| |
| 3) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: |
| GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN |
| EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED |
| PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY |
| SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE. |
| -WHICH METHOD OF COMPLIANCE IS BEING USED? |
| |
| 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT ARE |
| PART OF THE ALTERATION SHALL COMPLY WITH SECTION |
| R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH |
| R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5. |
| |
| 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| TILE ROOFING (TILE,UNDERLAYMENT AND ATTACHMENT), OR |
| INDICATE THAT YOU WOULD LIKE THEM DEFERED. |
| |
| NOTES: |
| |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |