Date |
Text |
2019-04-01 12:51:07 | PERMIT # 19031153 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| APPROVED PROVISO: |
| |
| 1) PROVIDE A KNOX KEY SWITCH TO ALLOW GATE ACCESS TO |
| EMERGENCY RESPONDERS. KEY SWITCH CAN BE ORDERED FROM |
| WWW.KNOXBOX.COM. |
| |
| 2) PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| WWW.KNOXBOX.COM. |
| |
| 3) PER SECTION 7.2.1.6.2, ACCESS-CONTROLLED EGRESS |
| DOORS ARE PERMITTED PROVIDED THAT ALL SEVEN OF THE |
| FOLLOWING CRITERIA ARE MET: |
| 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT |
| ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON |
| DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER |
| TO THE SENSOR. |
| 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL |
| SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK |
| THE DOORS IN THE DIRECTION OF EGRESS. |
| 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE |
| DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE |
| LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND |
| WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS. |
| 4. THE MANUAL RELEASE DEVICE SHALL BE READILY |
| ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS |
| PUSH TO EXIT. |
| 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK, |
| INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS, |
| AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN |
| 30 SECONDS. |
| 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL |
| AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER |
| SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL |
| AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| |
| |
| |
| SUE ELLEN CALDERON |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| |