| 1ST REVIEW: 19031107 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| FUEL GAS COMMENTS: |
| |
| 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 |
| FBC-R SEC. G2413.4.1, G2413.4.2. |
| |
| 2. SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. |
| |
| 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX |
| CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL |
| BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE |
| GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL |
| GAS SEC. 411.1.3.2. |
| |
| 4. PROVIDE DETAIL SHOWING CONNECTION AT THE GENERATOR |
| WITH SHUT VALVE AND DRIP LEG. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 5. STEEL PIPE IS NOT APPROVED FOR DIRECT BURIAL |
| UNDERGROUND IT SHALL BE SLEEVED PROVIDE DETAIL OF |
| SEALED SLEEVE AROUND PIPE. PER FBC FG 404.11 , 404.11.1 |
| |
| 6 SEPARATE PERMITS REQUIRED FOR THE GAS AND GENERATOR. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |