Permit Number |
19031079 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-08-05 15:04:55 | PLAN REVIEW COMMENTS | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | THE SUBMITTALS HAVE BEEN DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) ALL OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED | | WITH ONE EXCEPTION. THE RATIONAL ANALYSIS CALCULATIONS | | THAT WERE SUBMITTED FOR THE 24" X 24" ES 1500 FIXED | | WINDOWS IN ZONE 5 ARE INCORRECT. RATIONAL ANALYSIS CAN | | NOT BE USED TO INCREASE THE WIND LOAD PRESSURES FOR A | | TESTED ASSEMBLY. THE NEGATIVE AND POSITIVE PRESSURES OF | | +70, -80 PSF LISTED IN PRODUCT APPROVAL ARE BASED ON | | THE TESTING AND SAFETY FACTORS AS REQUIRED BY THE 2014 | | FBC SECTION 1710.5. |
|