2019-08-05 15:04:55PLAN REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 THE SUBMITTALS HAVE BEEN DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ALL OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED
 WITH ONE EXCEPTION. THE RATIONAL ANALYSIS CALCULATIONS
 THAT WERE SUBMITTED FOR THE 24" X 24" ES 1500 FIXED
 WINDOWS IN ZONE 5 ARE INCORRECT. RATIONAL ANALYSIS CAN
 NOT BE USED TO INCREASE THE WIND LOAD PRESSURES FOR A
 TESTED ASSEMBLY. THE NEGATIVE AND POSITIVE PRESSURES OF
 +70, -80 PSF LISTED IN PRODUCT APPROVAL ARE BASED ON
 THE TESTING AND SAFETY FACTORS AS REQUIRED BY THE 2014
 FBC SECTION 1710.5.