2019-06-07 10:27:44 | PLAN REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| THE SUBMITTALS HAVE BEEN DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) NOT ADDRESSED. THE BILCO ROOF HATCH, NOA NO |
| 18-0226.04, HAS A MAXIMUM DESIGN PRESSURE OF +/- 70 |
| PSF. THE ARCHITECTURAL AND STRUCTURAL ROOF PLANS SHOW |
| THAT PART OF THE HATCH IS LOCATED IN ROOF ZONE 2 AND |
| THE REST OF IT IS IN ROOF ZONE 1. THE REQUIRED NEGATIVE |
| PRESSURE FOR ROOF ZONE 2 IS - 126.9 PSF AND FOR ROOF |
| ZONE 1 IS -80.8 PSF , ACCORDING TO THE PRESSURES |
| DETERMINED BY THE STRUCTURAL ENGINEER ON SHEET S0.4 OF |
| THE PLANS. FBC 1609 AND 107.3.4 |
| |
| 2) NOT COMPLETELY ADDRESSED. THE NEW WINDOW/SLIDING |
| GLASS DOOR AND AC ROOF STAND SUBMITTALS DO NOT HAVE THE |
| DESIGNER OF RECORD'S SHOP REVIEW APPROVAL STAMP ON |
| THEM. THE DESIGNER OF RECORD FOR THE BUILDING IS |
| REQUIRED TO REVIEW AND APPROVE THE PRODUCT APPROVALS |
| FOR THE EXTERIOR DOORS AND WINDOWS, AS WELL AS, THE |
| SHOP DRAWINGS FROM THE SPECIALTY ENGINEER. FBC 107.3.4 |
| & 107.3.4.1 |
| |
| 3) NOT ADDRESSED. THESE WERE NOT RESUBMITTED. THE |
| SPECIALTY ENGINEER WHOSE NAME APPEARS IN THE TITLE |
| BLOCK IS REQUIRED TO SIGN, SEAL AND DATE THE WINDOW |
| WATERPROOFING DETAILS. 471.025, F.S., AND RULE |
| 61G15-23.001, F.A.C. |
| |
| 4) COMPLIED. |
| |
| 5) COMPLIED. |
| |
| 6) COMPLIED. |
| |
| 7) COMPLIED. |
| |
| 8) COMPLIED. |
| |
| 9) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |