2019-04-02 19:04:53 | PLAN REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| THE SUBMITTALS HAVE BEEN DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE BILCO ROOF HATCH, NOA NO 18-0226.04, HAS A |
| MAXIMUM DESIGN PRESSURE OF +/- 70 PSF. THE |
| ARCHITECTURAL AND STRUCTURAL ROOF PLANS SHOW THAT PART |
| OF THE HATCH IS LOCATED IN ROOF ZONE 2 AND THE REST OF |
| IT IS IN ROOF ZONE 1. THE REQUIRED NEGATIVE PRESSURE |
| FOR ROOF ZONE 2 IS - 126.9 PSF AND FOR ROOF ZONE 1 IS |
| -80.8 PSF , ACCORDING TO THE PRESSURES DETERMINED BY |
| THE STRUCTURAL ENGINEER ON SHEET S0.4 OF THE PLANS. FBC |
| 1609 AND 107.3.4 |
| |
| 2) THE DESIGNER OF RECORD FOR THE BUILDING IS REQUIRED |
| TO REVIEW AND APPROVE THE PRODUCT APPROVALS FOR THE |
| EXTERIOR DOORS AND WINDOWS, AS WELL AS, THE SHOP |
| DRAWINGS FROM THE SPECIALTY ENGINEER. FBC 107.3.4 & |
| 107.3.4.1 |
| |
| 3) THE SPECIALTY ENGINEER WHOSE NAME APPEARS IN THE |
| TITLE BLOCK IS REQUIRED TO SIGN, SEAL AND DATE THE |
| WINDOW WATERPROOFING DETAILS. 471.025, F.S., AND RULE |
| 61G15-23.001, F.A.C. |
| |
| 4) THERE WAS NO PRODUCT APPROVALS SUBMITTED FOR THE 20' |
| (240") WIDTH SLIDING GLASS DOOR (SGD) FRAME. THE TWO |
| DRAWINGS THAT WERE SUBMITTED HAVE A MAXIMUM FRAME WIDTH |
| OF 16' (192"). FBC 107.2.1 & FLORIDA STATUTE 553.842 |
| (5) |
| |
| 5) PLEASE INDICATE THE SPECIFIC DIMENSIONS, GLASS TYPE, |
| DESIGN PRESSURES, ETC. FOR THE WINDOWS AND EXTERIOR |
| DOORS THAT WILL BE INSTALLED BY MARKING THE APPROPRIATE |
| ITEMS FROM THE CHARTS THAT ARE LOCATED IN THE PRODUCT |
| APPROVALS. FBC 107.2.1 AND 1609. |
| |
| 6) NO FL PRODUCT APPROVAL COVER SHEET ASSOCIATED WITH |
| THE SGD DRAWING NUMBER W17-41 WAS SUBMITTED. FBC |
| 107.2.1 & FLORIDA STATUTE 553.842 (5) |
| |
| 7) THE GENERAL NOTES ON PAGE 1 OF THE SHOP DRAWINGS, |
| SPECIFY MIAMI-DADE NOA PRODUCT APPROVAL NUMBERS FOR THE |
| 6000 AND 6001 SERIES SGDS AND FLORIDA PRODUCT APPROVALS |
| WERE SUBMITTED. COORDINATE SUBMITTALS. FBC 107.2.1 |
| |
| 8) THE ELEVATION PRESSURES THAT ARE PROVIDED ON SHEET 1 |
| OF THE WINDOW AND SGD SHOP DRAWINGS ARE UNCLEAR AND ARE |
| NOT CONSISTENT WITH THE COMPONENT AND CLADDING |
| PRESSURES SPECIFIED BY THE ON SHEET S0.4. EITHER REMOVE |
| IT OR REVISE TO MATCH PLANS. FBC 107.2.1 & FBC 1609 |
| |