2019-04-10 16:27:43 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: |
| SUBMIT ALL THE INFORMATION OR CONTRACTOR TO ADVICE IF |
| PROVIDING COMPLETE INFORMATION UNDER A SEPARATE PERMIT. |
| |
| 1- PROVIDE COMPLETE MECHANICAL PLANS SHOWING ALL THE |
| DUCTWORK AND EQUIPMENT, ETC. CLEARLY SPECIFY EQUIPMENT |
| MANUFACTURER, MODEL, CAPACITY, ETC. 107.3.5.3 (11) CITY |
| AMENDMENTS. |
| |
| 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED |
| ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF |
| THE BUILDING. AND, THE MANUFACTURER'S AND MODEL NUMBER |
| SHALL BE SUBMITTED ALSO, ALONG WITH THE SENSIBLE AND |
| TOTAL COOLING CAPACITIES AS REQUIRED BY SEC. R403.7.1 |
| FBC-ENERGY CONSERVATION. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |