Plan Review Notes
Plan Review Notes For Permit 19031011
Permit Number 19031011
Review Stop E
Sequence Number 1
Notes
Date Text
2019-03-25 06:38:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL PLAN PROVIDED. PROVIDE ELECTRICAL PLAN
 FOR REVIEW, SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL. SHOW CONDUIT SIZE, CONDUIT TYPE, WIRE
 SIZE, MOTORS, OCP, HAZARDOUS LOCATION DOCUMENTATION,
 ETC. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1,
 107.3.5
  
 2, WORK HAS ALREADY BEEN COMPLETED IN THE FIELD WITH NO
 INSPECTIONS. LABELS ON EQUIPMENT AND EMAILS FROM
 CONTRACTOR STATE THAT IT IS A CLASS 1 DIVISION 1
 HAZARDOUS LOCATION. A DESIGN PROFESSIONAL MUST
 DETERMINE WHETHER IT IS A CLASS LOCATION OR NOT AND
 MUST PROVIDE SIGNED AND SEALED DOCUMENTION. NEC 500.4
 NEC 107.2.1
  
 3. VALUE FOR PROJECT LOW. RAISE VALUE OR VALUE WILL BE
 SET BY BUILDING OFFICIAL.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  