2019-04-16 08:21:05 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| |
| 1) DISCONNECT REQUIRED FOR SEPARATE STRUCTURE |
| |
| 225.30 NUMBER OF SUPPLIES |
| A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A |
| BRANCH CIRCUIT OR |
| FEEDER ON THE LOAD SIDE OF A SERVICE DISCONNECTING |
| MEANS SHALL BE |
| SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS |
| PERMITTED IN |
| 225.30(A) THROUGH (E). FOR THE PURPOSE OF THIS SECTION, |
| A MULTIWIRE |
| BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE CIRCUIT. |
| WHERE A BRANCH CIRCUIT OR FEEDER ORIGINATES IN THESE |
| ADDITIONAL |
| BUILDINGS OR OTHER STRUCTURES, ONLY ONE FEEDER OR |
| BRANCH CIRCUIT |
| SHALL BE PERMITTED TO SUPPLY POWER BACK TO THE ORIGINAL |
| BUILDING |
| OR STRUCTURE, UNLESS PERMITTED IN 225.30(A) THROUGH |
| (E). |
| |
| |
| 2) SEPARATE GROUNDING ELECTRODE SYSTEM REQUIRED. |
| |
| 250.32 BUILDINGS OR STRUCTURES SUPPLIED |
| BY A FEEDER(S) OR BRANCH CIRCUIT(S) |
| (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S) |
| SUPPLIED |
| BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A |
| GROUNDING ELECTRODE |
| OR GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE |
| WI TH |
| PART III OF ARTICLE 250. THE GROUNDING ELECTRODE |
| CONDUCTOR(S) SHALL |
| BE CON NECTED IN ACCORDANCE WITH 250.32(B) OR (C). |
| WHERE THERE |
| IS NO EXISTING GROUNDING ELECTRODE, THE GROUNDING |
| ELECTRODE(S) |
| REQUIRED IN 250.50 SHALL BE INSTALLED. |
| |
| 3) VALUE FOR WORK SEEMS LOW PLEASE SUBMIT A SIGNED |
| CONTRACT FOR WORK INVOLVOED. |