2019-04-17 11:55:23 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| SEC. 801.3 FBC-EXISTING BUILDING. |
| |
| 1- NEW MASTER BEDROOM: CLEARLY SPECIFY SIZE AND TYPE OF |
| EGRESS WINDOW TO VERIFY COMPLIANCE WITH THE CLEAR |
| OPENING REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. |
| NOTE: PLANS SUBMITTED ONLY SPECIFY EGRESS WINDOWS, BUT |
| DON'T SPECIFY TYPE AND SIZE. |
| |
| 2- SPECIFY TYPE AND SIZE OF EXISTING WINDOWS (SPECIALLY |
| THE BEDROOM WINDOWS) TO BE REPLACED AND TYPE AND SIZE |
| OF PROPOSED WINDOW TO VERIFY COMPLIANCE WITH THE EGRESS |
| REQUIREMENTS OF SEC. 702.5 FBC-EXISTING BUILDING. |
| NOTE: PLANS SUBMITTED ONLY SPECIFY EGRESS WINDOWS, BUT |
| DON'T SPECIFY TYPE AND SIZE. |
| |
| 3- ARCHITECT TO PROVIDE ALL THE WIND DESIGN CRITERIA AS |
| REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. SPECIFY THE |
| ULTIMATE AND NOMINAL WIND LOAD, BUILDING EXPOSURE, |
| BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE COMPONENTS |
| AND CLADDING DESIGN PRESSURES FOR DOORS AND WINDOWS. |
| |
| 4- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR ALL RELOCATED WINDOWS. CLEARLY SPECIFY ALL FRAMING |
| MEMBERS AND ALL CONNECTORS. PLANS SUBMITTED DON'T |
| PROVIDE ANY STRUCTURAL INFORMATION. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| 5- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR ALL INFILL EXTERIOR WALLS. CLEARLY SPECIFY ALL |
| FRAMING MEMBERS AND ALL CONNECTORS. THIS APPLIES TO |
| INTERIOR WALL PARTITIONS ALSO. CONNECTORS WERE NO |
| SPECIFIED ON DETAIL PROVIDED. PLANS SUBMITTED DON'T |
| PROVIDE ANY STRUCTURAL INFORMATION. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| 6- REVISE SPECIFICATIONS SHOWN ON TYPICAL NEW INFILL |
| EXTERIOR WALL ON SHEET A-001. |
| A)NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS |
| AS REQUIRED BY SEC. R703.7.3 WATER-RESISTIVE BARRIERS. |
| |
| B)NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS (NOT |
| 3/4") AS REQUIRED BY TABLE R702.1(1). |
| |
| 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) CASEMENT WINDOWS. NOA 17-1212.22 SUBMITTED EXPIRED |
| ON MARCH 04/2019. NEED TO PROVIDE CURRENT PRODUCT |
| APPROVAL. |
| |
| B) WINDOW MULLIONS (IF USED) PLANS ARE NOT CLEAR. |
| COORDINATE WITH ITEMS #1 AND #2 ABOVE. |
| AND, CLEARLY SPECIF MULLION SIZE TO VERIFY COMPLIANCE |
| WITH THE CALCULATED DESIGN PRESSURES. |
| |
| C) FRONT DOOR PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. |
| NEED TO PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL (2 |
| COPIES), INCLUDING THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED. THE |
| FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS |
| IF PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT. |
| |
| 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |