Plan Review Notes For Permit 19030971 |
Permit Number |
19030971 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-03-20 19:02:52 | RE-ROOF BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- THERE ARE SEVERAL ROOF AREAS IN THIS PROPERTY. IT IS | | NOT CLEAR WHICH AREA IS GOING TO BE RE-ROOF. SEC. | | 107.2.1 CITY AMENDMENTS. PROVIDE SKETCH (2 COPIES) | | SHOWING THE ACTUAL ROOF AREA AND TOTAL SQUARE FOOTAGE | | AREA TO BE RE-ROOFED AS REQUIRED BY CITY POLICY FOR ALL | | ROOFING PERMITS. | | | | 2- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R4 | | SUBMITTED: ACCORDING TO SEC. 1909.4 FBC THIS BUILDING | | IS LOCATED IN EXPOSURE "C" NOT EXPOSURE "B". REVISE THE | | EXPOSURE FOR NAIL ENHANCEMENT AT PERIMETER AND CORNER | | AREAS AS REQUIRED FOR EXPOSURE "C". | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|