2019-05-16 11:37:38 | SECOND BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| SEC. 801.3 FBC-EXISTING BUILDING. |
| |
| |
| 1- THERE IS A NOTE ON THE ENLARGEMENT DETAIL 1 ON SHEET |
| S200 STATING "EXISTING LIGHT GAUGE WALLS TO REMAIN. ANY |
| WALL THAT REQUIRED TO INSTALL THE NEW STEEL FRAMING |
| SHALL BE BUILT BACK PER THE ORIGINAL BASE BUILDING |
| DRAWINGS". |
| ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE DETAILS |
| AND SPECIFICATIONS FOR THE FRAMING OF THE WALL THAT IS |
| GOING TO BE BUILT TO RECEIVE THE NEW STOREFRONT. SEC. |
| 1609.1 FBC. |
| |
| RESPONSE: |
| RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT |
| "THE STOREFRONT SYSTEM SPANS VERTICALLY AND IS ATTACHED |
| TO THE SLAB ON GRADE AT THE BASE AND A NEW HSS MEMBER |
| AT THE HEAD PER SECTION 1/S320. THE LIGHT GAUGE WALLS |
| ARE INFILL EXTERIOR WALLS ONLY AND THEIR DESIGN IS BY |
| THE LIGHT GAUGE ENGINEER". |
| |
| THIS STATEMENT DOESN'T SEEM TO BE CORRECT. ACCORDING TO |
| STOREFRONT PRODUCT APPROVAL AND DETAILS SUBMITTED THE |
| STOREFRONT IS ATTACHED TO THE SIDE WALLS AS WELL. ALSO, |
| THERE WERE NO DETAILS AND SPECIFICATIONS SUBMITTED FROM |
| THE LIGHT GAUGE ENGINEER. |
| PROVIDE COMPLETE INFORMATION. |
| NOTE: COORDINATE WITH STOREFRONT PRODUCT APPROVAL TO |
| AVOID CONFLICTS/DELAYS. |
| |
| |
| 2- WALL SECTIONS ON SHEET S320 NEED TO PROVIDE COMPLETE |
| SPECIFICATIONS FOR THE CONSTRUCTION OF THE PARAPET. |
| NEED TO SPECIFY THE GAUGE OF THE STEEL STUDS AND |
| PROVIDE FASTENER SPECIFICATIONS. SEC. 1609.1 FBC. |
| |
| RESPONSE: |
| |
| RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT |
| "THE FINAL DESIGN OF THE LIGHT GAUGE STUDS WILL BE A |
| ""DIFFERENT SUBMITTAL"" SIGNED AND SEALED BY THE GC'S |
| ENGINEER". |
| |
| THE DIFFERED SUBMITTAL WAS NOT SUBMITTED. PROVIDE |
| COMPLETE INFORMATION. |
| |
| 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR THE NEW STOREFRONT SYSTEM AND DOORS |
| SPECIFIED ON PLANS. |
| |
| RESPONSE: |
| RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT |
| "PLEASE REFER TO ARCHITECTURAL SHEET A550 FOR TH |
| STOREFRONT AND DOOR ASSEMBLIES. THEY MATCH THE |
| PREVIOUSLY APPROVED NOA'S FOR THE BASE BUILDING". |
| |
| (A)PRODUCT APPROVALS SUBMITTED AND PRODUCT APPROVALS |
| LISTED ON SHEET A550 DON'T MATCH. REVISE AS REQUIRED TO |
| MATCH. |
| |
| (B) STOREFRONT ENGINEERED DRAWINGS SUBMITTED WITH THE |
| DOORS AND STOREFRONT PRODUCT APPROVALS NEED TO HAVE THE |
| ENGINEER'S (THOMAS J. TWOMEY) SEAL AND SIGNATURE AS |
| REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS |
| FOR PUBLIC RECORDS. ENGINEER DRAWINGS SUBMITTED |
| NOTE: THIS IS A DIGITAL SUBMITTAL. NEED DIGITAL |
| SIGNATURE ON DIGITAL SUBMITTALS. |
| |
| 4- OK. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |