Plan Review Notes
Plan Review Notes For Permit 19030914
Permit Number 19030914
Review Stop B
Sequence Number 2
Notes
Date Text
2019-05-16 11:37:38SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING.
  
  
 1- THERE IS A NOTE ON THE ENLARGEMENT DETAIL 1 ON SHEET
 S200 STATING "EXISTING LIGHT GAUGE WALLS TO REMAIN. ANY
 WALL THAT REQUIRED TO INSTALL THE NEW STEEL FRAMING
 SHALL BE BUILT BACK PER THE ORIGINAL BASE BUILDING
 DRAWINGS".
 ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS FOR THE FRAMING OF THE WALL THAT IS
 GOING TO BE BUILT TO RECEIVE THE NEW STOREFRONT. SEC.
 1609.1 FBC.
  
 RESPONSE:
 RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT
 "THE STOREFRONT SYSTEM SPANS VERTICALLY AND IS ATTACHED
 TO THE SLAB ON GRADE AT THE BASE AND A NEW HSS MEMBER
 AT THE HEAD PER SECTION 1/S320. THE LIGHT GAUGE WALLS
 ARE INFILL EXTERIOR WALLS ONLY AND THEIR DESIGN IS BY
 THE LIGHT GAUGE ENGINEER".
  
 THIS STATEMENT DOESN'T SEEM TO BE CORRECT. ACCORDING TO
 STOREFRONT PRODUCT APPROVAL AND DETAILS SUBMITTED THE
 STOREFRONT IS ATTACHED TO THE SIDE WALLS AS WELL. ALSO,
 THERE WERE NO DETAILS AND SPECIFICATIONS SUBMITTED FROM
 THE LIGHT GAUGE ENGINEER.
 PROVIDE COMPLETE INFORMATION.
 NOTE: COORDINATE WITH STOREFRONT PRODUCT APPROVAL TO
 AVOID CONFLICTS/DELAYS.
  
  
 2- WALL SECTIONS ON SHEET S320 NEED TO PROVIDE COMPLETE
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE PARAPET.
 NEED TO SPECIFY THE GAUGE OF THE STEEL STUDS AND
 PROVIDE FASTENER SPECIFICATIONS. SEC. 1609.1 FBC.
  
 RESPONSE:
  
 RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT
 "THE FINAL DESIGN OF THE LIGHT GAUGE STUDS WILL BE A
 ""DIFFERENT SUBMITTAL"" SIGNED AND SEALED BY THE GC'S
 ENGINEER".
  
 THE DIFFERED SUBMITTAL WAS NOT SUBMITTED. PROVIDE
 COMPLETE INFORMATION.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR THE NEW STOREFRONT SYSTEM AND DOORS
 SPECIFIED ON PLANS.
  
 RESPONSE:
 RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT
 "PLEASE REFER TO ARCHITECTURAL SHEET A550 FOR TH
 STOREFRONT AND DOOR ASSEMBLIES. THEY MATCH THE
 PREVIOUSLY APPROVED NOA'S FOR THE BASE BUILDING".
  
 (A)PRODUCT APPROVALS SUBMITTED AND PRODUCT APPROVALS
 LISTED ON SHEET A550 DON'T MATCH. REVISE AS REQUIRED TO
 MATCH.
  
 (B) STOREFRONT ENGINEERED DRAWINGS SUBMITTED WITH THE
 DOORS AND STOREFRONT PRODUCT APPROVALS NEED TO HAVE THE
 ENGINEER'S (THOMAS J. TWOMEY) SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS. ENGINEER DRAWINGS SUBMITTED
 NOTE: THIS IS A DIGITAL SUBMITTAL. NEED DIGITAL
 SIGNATURE ON DIGITAL SUBMITTALS.
  
 4- OK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  