2019-04-04 09:00:55PERMIT # 19030914
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 2) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 3) SEPARATE PERMITS REQUIRED FOR ALL WORK DONE RELATED
 TO THE FIRE ALARM AND SPRINKLER SYSTEM.
  
 4) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  