Plan Review Notes
Plan Review Notes For Permit 19030913
Permit Number 19030913
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-03-22 11:16:54PERMIT # 19030913
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) IF NOT ALREADY INCLUDED, PROVIDE DRAWING NOTE
 INDICATING ALL CONSTRUCTION AND DEMOLITION WORK SHALL
 CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH AND
 CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 2) IF NOT ALREADY INCLUDED, PROVIDE DRAWING NOTE
 INDICATING, ?FIRE PROTECTION SYSTEMS SHALL REMAIN
 ACTIVE DURING DEMOLITION AND RENOVATION ACTIVITIES. IN
 THE EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE
 FOR MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED BY EMAIL ([email protected])
 OR IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE
 OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE
 HIGHWAY.?
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  