2019-04-09 16:44:471ST REVIEW FBC-2017 MECHANICAL
 REVISION #19030907
 4/9/19
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SIGNATURE OF CONTRACTOR OR QUALIFIER ON PLANS
 REQUIRED: SEE FLORIDA STATUTE 633.021, AND SECTION
 107.2.1 FBC. WPB AMENDMENTS TO THE FBC: ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 2) SHOW THE CFMS AT EACH SUPPLY DIFFUSER AND EACH
 RETURN GRILL- SECTION R403.7.1 FBC EC.
  
 3) PROVIDE A HATCH FOR ACCESS TO THE AIR HANDLER IN THE
 ATTIC- SEE SECTION M1305.1 FBC R AND SECTIONS R402.2.4&
 R403.3.6 FBC EC FOR COMPLAUINCE REQUIREMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  