2019-04-09 16:44:47 | 1ST REVIEW FBC-2017 MECHANICAL |
| REVISION #19030907 |
| 4/9/19 |
| |
| CODES IN EFFECT: |
| |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SIGNATURE OF CONTRACTOR OR QUALIFIER ON PLANS |
| REQUIRED: SEE FLORIDA STATUTE 633.021, AND SECTION |
| 107.2.1 FBC. WPB AMENDMENTS TO THE FBC: ALL |
| INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. |
| |
| 2) SHOW THE CFMS AT EACH SUPPLY DIFFUSER AND EACH |
| RETURN GRILL- SECTION R403.7.1 FBC EC. |
| |
| 3) PROVIDE A HATCH FOR ACCESS TO THE AIR HANDLER IN THE |
| ATTIC- SEE SECTION M1305.1 FBC R AND SECTIONS R402.2.4& |
| R403.3.6 FBC EC FOR COMPLAUINCE REQUIREMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |