2019-06-13 15:20:50 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 30A |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 4TH REVIEW; CONDUCTED BY JERALD SMITH; PHONE |
| 561-805-6715 |
| PLUMBING COMMEMTS: DENIED |
| NOTE |
| * PER FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF |
| DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT |
| FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH |
| THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| REVIEW.*** |
| * ARCHITECTURAL COMMENTS AND RESPONSES ATTACHED TO |
| PLANS SEEM TO BE DIRECTED AT THE SECOND PLUMBING REVIEW |
| DATED 5/6/19 AND NOT THE LATEST REVIEW DATED 5/28/19. |
| ADDITIONALLY, REVISION DATES, SPECIFICALLY ON PLAN |
| SHEET A6.0 DO NOT ADDRESS THE THIRD REVIEW DATED |
| 5/28/19. |
| * DO NOT RESUBMIT WITHOUT FIRST HOLDING A SCHEDULED |
| MEETING WITH THE PLANS EXAMINER(S) TO RESOLVE THE |
| ISSUES. PLEASE CONTACT SAMANTHA HILL AT 805-6724 FOR |
| SCHEDULING. |
| PLEASE NOTE THAT PLUMBING WILL NOT BE APPROVED UNTIL |
| THE ISSUES ON THE ARCHITECTURAL PLANS HAVE BEEN |
| CORRECTLY ADDRESSED |
| 1. 4TH REQUEST- ARCHITECTURAL ISSUE: PLAN SHEET A6.0; |
| THE LOCATION OF THE REAR GRAB BAR SHALL COMPLY WITH |
| FBC-ACCESS. SEC.604.5.2. 24" OPPOSITE THE 12" NOT SHOWN |
| ON DETAIL (GRAB BAR AT WATER CLOSET) SHT. A6.0. TO |
| CLARIFY THE DETAIL, DIMENSION FROM CENTER OF WATER |
| CLOSET TO LEFT SHALL BE 24? MIN., NOT 12?. |
| ADDITIONALLY, THE DETAIL NOW DOES NOT COMPLY WITH FBC |
| ACC 604.2, REQUIRING A SIDE WALL WITH THE CENTERLINE |
| WATER CLOSET DIMENSION BEING 16?-18?. SEE FIGURE 604.2 |
| FOR CLARITY. |
| 2. 4TH REQUEST-PLAN SHEET P-2: PLUMBING GENERAL NOTE #1 |
| REFERS TO THE 2014 FBC. THE CODE IN EFFECT IS THE 2017 |
| FBC. REVISE AND RESUBMIT. NOT ADDRESSED |
| 3. 4TH REQUEST-PER WPB FBC 107.2.1, SUBMIT |
| MANUFACTURER'S SPECIFICATIONS FOR THE TANKLESS WATER |
| HEATERS. NOT ADDRESSED, WILL ALLOW DEFERRED SUBMITTAL |
| 4. 2ND REQUEST- ARCHITECTURAL ISSUE: THIS IS APPROVED |
| SHT. A6.0 DETAIL #9 SHOWS GRAB BARS MEASURED TO THE |
| ESCUTCHEON RING; THE DETAIL FOR THE GRAB BARS AT WATER |
| CLOSET SHOWS MEASURED TO THE CENTER OF THE GRAB BAR, |
| THEY BOTH SHALL SHOW MEASURED TO THE TOP OF THE |
| GRIPPING SURFACE. FBC ACC 609.4. PLEASE NOTE THAT |
| DETAIL #7 BATHROOM BACKING DETAIL CORRECTLY SHOWS THE |
| REQUIREMENTS. RECONCILE DETAIL #9 WITH #7. |
| 5. REGARDING THE FOLLOWING COMMENTS MADE DURING THE |
| SECOND REVIEW CONCERNING THE SHOWER IN THE TOILET RM W/ |
| SHOWER STAFF RM #110, PLEASE NOTE: |
| A. ARCHITECTURAL ISSUE: SHT. A6.0 DETAIL #5 THE |
| ACCESSIBLE SHOWER DETAIL DOES NOT MATCH DETAIL #1 |
| ENLARGED BATHROOM THE SHOWER SHALL COMPLY WITH FBC ACC |
| 608.2.2.1, 608.3.2, 608.5.2. NOTE THAT THE SPACE AND |
| CONFIGURATION ALLOWED BY THE ARCHITECT DOES NOT MEET |
| THE REQUIREMENTS FOR A STANDARD ROLL IN SHOWER |
| COMPARTMENT. |
| B. ARCHITECTURAL ISSUE: THE SEAT IS BEING SHOWN ON THE |
| SAME SIDE AS THE END GRAB BAR IT SHALL BE ON THE |
| OPPOSITE END IT WILL BE DIFFICULT TO COMPLY WITH THE |
| ANGLE WALL. FBC ACC 608.3.2. THE ARCHITECT HAS MOVED |
| THE SEAT TO THE OPPOSITE SIDE OF THE SHOWER STALL ON |
| A6.0, DETAIL 1. ADDITIONALLY, HE HAS MADE THE STALL 36? |
| WIDE AND OFFSET THE SEAT TO THE CURB SIDE OF THE SHOWER |
| (DUE TO AN OBSTRUCTION LESS THAN 10?) AS OPPOSED TO |
| BEING WITHIN 30? MINIMUM WIDTH SPACE, INCREASING THE |
| SIDE REACH SPACE BETWEEN THE USER AND GRAB BARS BY 6?. |
| PLEASE REVIEW FBC ACC 308.3, 308.3.1, (1), (2), |
| 308.3.2, (1), (2) AND 309 FOR COMPLIANCE AND NOTE |
| ACTUAL OBSTRUCTION DIMENSION (I.E. 6? OBSTRUCTION DUE |
| TO ANGLE WALL) IF APPLICABLE ON PLAN SHEET A6.0, DETAIL |
| 1. |
| C. ARCHITECTURAL ISSUE: THE ENDS OF THE GRAB BARS SHALL |
| BE 6" MAX FROM ADJACENT WALL. FBC ACC 608.3.2. THIS IS |
| APPROVED |
| D. ARCHITECTURAL ISSUE: SHOW CLEAR FLOW SPACE FOR |
| SHOWER. FBC ACC 608.2.2.1. NOT ADDRESSED |
| 6. ADDITIONAL COMMENTS (3D REVIEW) CONCERNING TOILET RM |
| W/ SHOWER STAFF RM #110: |
| A. ARCHITECTURAL ISSUE: FBC ACC 604.2 REQUIRES THAT THE |
| WATER CLOSET POSITIONED WITH A WALL OR PARTITION TO THE |
| REAR AND ONE SIDE OF THE FIXTURE; SIDE AND REAR HAND |
| BARS SHALL CONFORM TO FBC ACC 604.5.1 AND 605.2. A |
| PULLDOWN GRAB BAR IS NOT COMPLIANT AND SHALL NOT BE |
| USED. TO BE CLEAR, THIS COMMENT WAS DIRECTED AT THE |
| TOILET ROOM WITH SHOWER AND HAS NOT BEEN ADDRESSED. |
| FURTHERMORE, AS A PULLDOWN GRAB BAR IS NOT COMPLIANT, |
| PLEASE REMOVE DETAIL 10 FROM PLAN SHEET A6.0. |
| B. ARCHITECTURAL ISSUE: FBC ACC 604.7 REQUIRES TOILET |
| PAPER DISPENSER TO BE LOCATED ON THE SIDE WALL 7?-9? |
| FRONT OF THE WATER CLOSET TO CENTER OF DISPENSER AND |
| INSIDE THE SPACE OF 15? MINIMUM TO 48?? MAXIMUM ABOVE |
| THE FLOOR. TO BE CLEAR, THIS COMMENT WAS DIRECTED AT |
| THE TOILET ROOM WITH SHOWER AND HAS NOT BEEN ADDRESSED. |
| C. ARCHITECTURAL ISSUE: NOTE THAT PER 604.8.1.2, THE |
| ENTRY DOOR SHALL BE LOCATED IN THE FRONT PARTITION OR |
| IN THE SIDE WALL OR PARTITION FARTHEST FROM THE WATER |
| CLOSET. WHERE LOCATED IN THE FRONT PARTITION, THE DOOR |
| OPENING SHALL BE 4 INCHES (100 MM) MAXIMUM FROM THE |
| SIDE WALL OR PARTITION FARTHEST FROM THE WATER CLOSET. |
| WHERE LOCATED IN THE SIDE WALL OR PARTITION, THE DOOR |
| OPENING SHALL BE 4 INCHES (100 MM) MAXIMUM FROM THE |
| FRONT PARTITION. TO BE CLEAR, THIS COMMENT WAS DIRECTED |
| AT THE TOILET ROOM WITH SHOWER AND HAS NOT BEEN |
| ADDRESSED. |
| |
| 7. 3RD REVIEW ADDITIONAL COMMENTS |
| A. PLAN SHEET P-1 AND P-3; MOP SINK LOCATION. RECONCILE |
| SANITARY ISOMETRIC ON P-3 WITH THE FLOOR PLAN ON P-1. |
| NOT ADDRESSED |
| B. REGARDING THE FOLLOWING ORIGINAL COMMENT: TEMPERED |
| WATER IS REQUIRED AT THE LAVATORIES IN THE TOILET ROOMS |
| AND BATHROOM PER FBC-PLUMBING. SEC. 416.5. TEMPERED |
| WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. PER WPB FBC 107.2.1, PROVIDE CUT |
| SHEET AND SPEC FOR OWNER FURNISHED WALL MOUNTED, ADA |
| COMPLIANT ANTI-SCALD VALVE SHOWING COMPLIANCE WITH ASSE |
| 1070 OR CSA B125.3 AS REQUIRED BY FBC PL 416.5 FOR THE |
| HANDICAPPED LAVATORIES. ALSO PROVIDE A DETAIL OF |
| INSTALLATION TO SHOW COMPLIANCE WITH FBC ACC 309. NOT |
| ADDRESSED, WILL ALLOW DEFERRED SUBMITTAL |
| 4TH REVIEW ADDITIONAL COMMENTS |
| 1. RE: PLAN SHEET A6.0, ACCESSIBLE DETAIL 5; THRESHOLD |
| SHALL BE A MAXIMUM OF ?? PER FBC ACC 608.7 AND GRAB |
| BARS SHALL BE 33? MINIMUM-36? MAXIMUM TO TOP SURFACE OF |
| GRAB BAR. |
| 2. RE: PLAN SHEET A7.0, DETAIL C; DIMENSION 2?-10? |
| MAXIMUM TO RIM OF FIXTURE NOT TO TOP OF CABINET AS RIM |
| IS HIGHER THAN THE CABINET TOP PER FBC ACC 606.3. |
| 3. RE: PLAN SHEET A6.0, ACCESSIBLE WATER FOUNTAIN |
| DETAIL; PROVIDE KNEE AND TOE CLEARANCES CONFORMING TO |
| FBC ACC 306.2 AND 306.3 AND CONFORM TO FBC ACC 602.4 |
| AND 602.5. |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |