Plan Review Notes
Plan Review Notes For Permit 19030897
Permit Number 19030897
Review Stop P
Sequence Number 4
Notes
Date Text
2019-06-13 15:20:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 4TH REVIEW; CONDUCTED BY JERALD SMITH; PHONE
 561-805-6715
 PLUMBING COMMEMTS: DENIED
 NOTE
 * PER FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF
 DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT
 FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH
 THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.***
 * ARCHITECTURAL COMMENTS AND RESPONSES ATTACHED TO
 PLANS SEEM TO BE DIRECTED AT THE SECOND PLUMBING REVIEW
 DATED 5/6/19 AND NOT THE LATEST REVIEW DATED 5/28/19.
 ADDITIONALLY, REVISION DATES, SPECIFICALLY ON PLAN
 SHEET A6.0 DO NOT ADDRESS THE THIRD REVIEW DATED
 5/28/19.
 * DO NOT RESUBMIT WITHOUT FIRST HOLDING A SCHEDULED
 MEETING WITH THE PLANS EXAMINER(S) TO RESOLVE THE
 ISSUES. PLEASE CONTACT SAMANTHA HILL AT 805-6724 FOR
 SCHEDULING.
 PLEASE NOTE THAT PLUMBING WILL NOT BE APPROVED UNTIL
 THE ISSUES ON THE ARCHITECTURAL PLANS HAVE BEEN
 CORRECTLY ADDRESSED
 1. 4TH REQUEST- ARCHITECTURAL ISSUE: PLAN SHEET A6.0;
 THE LOCATION OF THE REAR GRAB BAR SHALL COMPLY WITH
 FBC-ACCESS. SEC.604.5.2. 24" OPPOSITE THE 12" NOT SHOWN
 ON DETAIL (GRAB BAR AT WATER CLOSET) SHT. A6.0. TO
 CLARIFY THE DETAIL, DIMENSION FROM CENTER OF WATER
 CLOSET TO LEFT SHALL BE 24? MIN., NOT 12?.
 ADDITIONALLY, THE DETAIL NOW DOES NOT COMPLY WITH FBC
 ACC 604.2, REQUIRING A SIDE WALL WITH THE CENTERLINE
 WATER CLOSET DIMENSION BEING 16?-18?. SEE FIGURE 604.2
 FOR CLARITY.
 2. 4TH REQUEST-PLAN SHEET P-2: PLUMBING GENERAL NOTE #1
 REFERS TO THE 2014 FBC. THE CODE IN EFFECT IS THE 2017
 FBC. REVISE AND RESUBMIT. NOT ADDRESSED
 3. 4TH REQUEST-PER WPB FBC 107.2.1, SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE TANKLESS WATER
 HEATERS. NOT ADDRESSED, WILL ALLOW DEFERRED SUBMITTAL
 4. 2ND REQUEST- ARCHITECTURAL ISSUE: THIS IS APPROVED
 SHT. A6.0 DETAIL #9 SHOWS GRAB BARS MEASURED TO THE
 ESCUTCHEON RING; THE DETAIL FOR THE GRAB BARS AT WATER
 CLOSET SHOWS MEASURED TO THE CENTER OF THE GRAB BAR,
 THEY BOTH SHALL SHOW MEASURED TO THE TOP OF THE
 GRIPPING SURFACE. FBC ACC 609.4. PLEASE NOTE THAT
 DETAIL #7 BATHROOM BACKING DETAIL CORRECTLY SHOWS THE
 REQUIREMENTS. RECONCILE DETAIL #9 WITH #7.
 5. REGARDING THE FOLLOWING COMMENTS MADE DURING THE
 SECOND REVIEW CONCERNING THE SHOWER IN THE TOILET RM W/
 SHOWER STAFF RM #110, PLEASE NOTE:
 A. ARCHITECTURAL ISSUE: SHT. A6.0 DETAIL #5 THE
 ACCESSIBLE SHOWER DETAIL DOES NOT MATCH DETAIL #1
 ENLARGED BATHROOM THE SHOWER SHALL COMPLY WITH FBC ACC
 608.2.2.1, 608.3.2, 608.5.2. NOTE THAT THE SPACE AND
 CONFIGURATION ALLOWED BY THE ARCHITECT DOES NOT MEET
 THE REQUIREMENTS FOR A STANDARD ROLL IN SHOWER
 COMPARTMENT.
 B. ARCHITECTURAL ISSUE: THE SEAT IS BEING SHOWN ON THE
 SAME SIDE AS THE END GRAB BAR IT SHALL BE ON THE
 OPPOSITE END IT WILL BE DIFFICULT TO COMPLY WITH THE
 ANGLE WALL. FBC ACC 608.3.2. THE ARCHITECT HAS MOVED
 THE SEAT TO THE OPPOSITE SIDE OF THE SHOWER STALL ON
 A6.0, DETAIL 1. ADDITIONALLY, HE HAS MADE THE STALL 36?
 WIDE AND OFFSET THE SEAT TO THE CURB SIDE OF THE SHOWER
 (DUE TO AN OBSTRUCTION LESS THAN 10?) AS OPPOSED TO
 BEING WITHIN 30? MINIMUM WIDTH SPACE, INCREASING THE
 SIDE REACH SPACE BETWEEN THE USER AND GRAB BARS BY 6?.
 PLEASE REVIEW FBC ACC 308.3, 308.3.1, (1), (2),
 308.3.2, (1), (2) AND 309 FOR COMPLIANCE AND NOTE
 ACTUAL OBSTRUCTION DIMENSION (I.E. 6? OBSTRUCTION DUE
 TO ANGLE WALL) IF APPLICABLE ON PLAN SHEET A6.0, DETAIL
 1.
 C. ARCHITECTURAL ISSUE: THE ENDS OF THE GRAB BARS SHALL
 BE 6" MAX FROM ADJACENT WALL. FBC ACC 608.3.2. THIS IS
 APPROVED
 D. ARCHITECTURAL ISSUE: SHOW CLEAR FLOW SPACE FOR
 SHOWER. FBC ACC 608.2.2.1. NOT ADDRESSED
 6. ADDITIONAL COMMENTS (3D REVIEW) CONCERNING TOILET RM
 W/ SHOWER STAFF RM #110:
 A. ARCHITECTURAL ISSUE: FBC ACC 604.2 REQUIRES THAT THE
 WATER CLOSET POSITIONED WITH A WALL OR PARTITION TO THE
 REAR AND ONE SIDE OF THE FIXTURE; SIDE AND REAR HAND
 BARS SHALL CONFORM TO FBC ACC 604.5.1 AND 605.2. A
 PULLDOWN GRAB BAR IS NOT COMPLIANT AND SHALL NOT BE
 USED. TO BE CLEAR, THIS COMMENT WAS DIRECTED AT THE
 TOILET ROOM WITH SHOWER AND HAS NOT BEEN ADDRESSED.
 FURTHERMORE, AS A PULLDOWN GRAB BAR IS NOT COMPLIANT,
 PLEASE REMOVE DETAIL 10 FROM PLAN SHEET A6.0.
 B. ARCHITECTURAL ISSUE: FBC ACC 604.7 REQUIRES TOILET
 PAPER DISPENSER TO BE LOCATED ON THE SIDE WALL 7?-9?
 FRONT OF THE WATER CLOSET TO CENTER OF DISPENSER AND
 INSIDE THE SPACE OF 15? MINIMUM TO 48?? MAXIMUM ABOVE
 THE FLOOR. TO BE CLEAR, THIS COMMENT WAS DIRECTED AT
 THE TOILET ROOM WITH SHOWER AND HAS NOT BEEN ADDRESSED.
 C. ARCHITECTURAL ISSUE: NOTE THAT PER 604.8.1.2, THE
 ENTRY DOOR SHALL BE LOCATED IN THE FRONT PARTITION OR
 IN THE SIDE WALL OR PARTITION FARTHEST FROM THE WATER
 CLOSET. WHERE LOCATED IN THE FRONT PARTITION, THE DOOR
 OPENING SHALL BE 4 INCHES (100 MM) MAXIMUM FROM THE
 SIDE WALL OR PARTITION FARTHEST FROM THE WATER CLOSET.
 WHERE LOCATED IN THE SIDE WALL OR PARTITION, THE DOOR
 OPENING SHALL BE 4 INCHES (100 MM) MAXIMUM FROM THE
 FRONT PARTITION. TO BE CLEAR, THIS COMMENT WAS DIRECTED
 AT THE TOILET ROOM WITH SHOWER AND HAS NOT BEEN
 ADDRESSED.
  
 7. 3RD REVIEW ADDITIONAL COMMENTS
 A. PLAN SHEET P-1 AND P-3; MOP SINK LOCATION. RECONCILE
 SANITARY ISOMETRIC ON P-3 WITH THE FLOOR PLAN ON P-1.
 NOT ADDRESSED
 B. REGARDING THE FOLLOWING ORIGINAL COMMENT: TEMPERED
 WATER IS REQUIRED AT THE LAVATORIES IN THE TOILET ROOMS
 AND BATHROOM PER FBC-PLUMBING. SEC. 416.5. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. PER WPB FBC 107.2.1, PROVIDE CUT
 SHEET AND SPEC FOR OWNER FURNISHED WALL MOUNTED, ADA
 COMPLIANT ANTI-SCALD VALVE SHOWING COMPLIANCE WITH ASSE
 1070 OR CSA B125.3 AS REQUIRED BY FBC PL 416.5 FOR THE
 HANDICAPPED LAVATORIES. ALSO PROVIDE A DETAIL OF
 INSTALLATION TO SHOW COMPLIANCE WITH FBC ACC 309. NOT
 ADDRESSED, WILL ALLOW DEFERRED SUBMITTAL
 4TH REVIEW ADDITIONAL COMMENTS
 1. RE: PLAN SHEET A6.0, ACCESSIBLE DETAIL 5; THRESHOLD
 SHALL BE A MAXIMUM OF ?? PER FBC ACC 608.7 AND GRAB
 BARS SHALL BE 33? MINIMUM-36? MAXIMUM TO TOP SURFACE OF
 GRAB BAR.
 2. RE: PLAN SHEET A7.0, DETAIL C; DIMENSION 2?-10?
 MAXIMUM TO RIM OF FIXTURE NOT TO TOP OF CABINET AS RIM
 IS HIGHER THAN THE CABINET TOP PER FBC ACC 606.3.
 3. RE: PLAN SHEET A6.0, ACCESSIBLE WATER FOUNTAIN
 DETAIL; PROVIDE KNEE AND TOE CLEARANCES CONFORMING TO
 FBC ACC 306.2 AND 306.3 AND CONFORM TO FBC ACC 602.4
 AND 602.5.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19030897 1411 N FLAGLER DR # 8900