| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19030897 |
| ADD: 1411 N. FLAGLER DRIVE SUITE 8900 |
| CONT: LEIGHTON MCGINN |
| TEL: 561863-4455 |
| E-MAIL: [email protected] |
| |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| |
| 4TH REVIEW |
| DATE: 06/17/19 |
| ACTION: DENIED |
| |
| ORIGINAL COMMENT: |
| 1) THE COVERSHEET UNDER APPLICABLE CODES LIST THE |
| BUILDING TYPE AS A TYPE V(A) UNSPRINKLERED. PLEASE |
| REVIEW THE BUILDING AND SITE. THE VICTOR FARRIS |
| BUILDING IS A 9 STORY HIGHRISE, FULLY SPRINKLERED. |
| PLEASE UPDATE THE PLANS TO THE CORRECT BUILDING TYPE. |
| SEE THE 2017 FBC-B TABLE 504.4. |
| |
| RESPONSE: |
| REPEAT COMMENT. FOUR TIMES. PLANS SUBMITTED SHOW SAME |
| INFORMATION FROM LAST BUILDING REVIEW. |
| BUILDING TYPE WAS REVISED TO TYPE II(A)SPRINKLERED. |
| THIS IS INCORRECT AGAIN. ACCORDING TO TABLE 504.4 |
| FBC-BUILDING THE MAXIMUM NUMBER OF STORIES ABOVE GRADE |
| PLANE ALLOWED FOR TYPE II(A) SPRINKLERED BUILDING FOR A |
| BUSINESS OCCUPANCY IS 6 STORIES. SEE TABLE 504.4 AND |
| REVISE AS REQUIRED. |
| |
| |
| 2)OK. |
| |
| 3)OK. |
| |
| 4) OK. |
| |
| 5) LIFE SAFETY SHEET: |
| |
| 5A)OK. |
| |
| 5B)OK. |
| |
| ORIGINAL COMMENT: |
| 5C) THE OTHER ISSUE WITH THE RECEPTION/ CONFERENCE ROOM |
| OCCUPANT LOAD IS THE COMMON PATH OF TRAVEL. |
| SEE TABLE 1006.2.1 THE MAXIMUM OCCUPANT LOAD OF 30 |
| OCCUPANTS IN THE ASSEMBLY OCCUPANCY THE COMMON PATH OF |
| TRAVEL IS LIMITED TO 75 FEET AND THE MAXIMUM OCCUPANT |
| LOAD OF 49, TABLE 1006.1.2. |
| |
| PLEASE REVIEW SECTION 1006.2.1 EGRESS BASED ON OCCUPANT |
| LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE. TWO |
| EXITS OR EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE |
| PROVIDED WHERE THE DESIGN OCCUPANT LOAD OR THE COMMON |
| PATH OF EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES |
| LISTED IN TABLE 1006.2.1. THE EXCEPTION FORI-2 DOES NOT |
| WORK SINCE THIS IS NOT A CARE SUITE WITHIN A HOSPITAL. |
| PLEASE PROVIDE 2 EXIT ACCESS DOORWAY THAT WILL BE IN |
| COMPLIANCE WITH FBC-B 1007.1.1 EXCEPTION2. |
| FBC-B 1007.1.1 EXCEPTION2. WHERE A BUILDING IS EQUIPPED |
| THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2, THE |
| SEPARATION DISTANCE SHALL BE NOT LESS THAN ONE-THIRD OF |
| THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF |
| THE AREA SERVED. |
| |
| THERE ARE 2 AREAS OF CONCERN, 1ST IN THE CONFERENCE |
| ROOM ITSELF REQUIRING 2 MEANS OF EGRESS, OUTSWING DOOR |
| REQUIRED. THE 2ND AREA IS WITHIN THE TENANT SPACE |
| ITSELF THE TOTAL OCCUPANT LOAD IS OVER 49 REQUIRING |
| ALSO 2 MEANS OF EGRESS. |
| |
| RESPONSE: |
| REPEAT COMMENT. FOUR TIMES. (ARCHITECT TO SEE FLORIDA |
| STATUTE 553.80(2)(B)). FEES WILL APPLY. |
| |
| TENANT SPACE PROPOSED SECOND MEANS OF EGRESS DOESN'T |
| COMPLY WITH EXCEPTION #2 OF SEC. 1007.1.1 FBC-BUILDING. |
| THE SEPARATION DISTANCE SHALL BE NOT LESS THAN |
| ONE-THIRD OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL |
| DIMENSION OF THE AREA SERVED. THE DIAGONAL DISTANCE |
| SHOWN IS 95'-0". ONE THIRD 1/3 OF 95'-0" IS 31'-8". THE |
| DISTANCE BETWEEN THE TWO EXITS IS +/- 22'-0". |
| THEREFORE, IT DOESN'T COMPLY. REVISE AS REQUIRED. |
| NOTE: THE DISTANCE IS MEASURED THE SAME WAY THE |
| DIAGONAL DIMENSION IS DIMENSIONED. IS THE DISTANCE |
| BETWEEN THE TWO DOORS NOT THE TRAVEL DISTANCE BETWEEN |
| THE TWO DOORS AS SHOWN ON PLAN. REVISE AS REQUIRED. |
| ALSO, PLEASE CLEAN UP INFORMATION ON PLANS. THERE ARE |
| SOME DIMENSIONS THAT CORRESPOND TO PREVIOUS PLANS THAT |
| NO LONGER APPLIES. FOR EXAMPLE, SEE THE TRAVEL DISTANCE |
| 95'-0" SHOWN BY THE CONFERENCE ROOM AND TOTAL TRAVEL |
| DISTANCE SHOWN BY THE ENTRY DOOR. PLEASE MAKE SURE ALL |
| REVISED FLOOR PLANS MATCH. OFFICE LAYOUT SHOWN BY THE |
| SECOND PROPOSED EXIT DOESN'T MATCH. |
| |
| NOTE: SCALE SHOWN ON SHEET A2.0 AND A3.0 IS INCORRECT. |
| REVISE AS REQUIRED. |
| |
| ARCHITECTS-ENGINEERS |
| FLORIDA STATUTE 553.80(2)(B): |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| |
| |
| |
| 6) SHEET A6.0 ACCESSIBLE FEATURES: |
| |
| THE FOLLOWING COMMENTS APPLY TO THE SHOWER COMPARTMENT |
| BASED ON REVISIONS DONE TO ADDRESSEES ORIGINAL COMMENTS |
| REGARDING ACCESSIBLE FEATURES. |
| |
| SHOWER COMPARTMENT (SEC. 608 FBC-ACCESSIBILITY): |
| A)OK. |
| |
| B) OK. |
| |
| ORIGINAL COMMENT: |
| C) IT IS NOT CLEAR WHAT IS THE 2'-8" DIMENSION SHOWN BY |
| THE SHOWER AREA. IS THERE A PARTITION BETWEEN THE WATER |
| CLOSET AND THE SHOWER?. SEC. 107.2.1 CITY AMENDMENTS |
| AND SEC. 608.2.2.1 |
| |
| RESPONSE: |
| STILL NO CLEAR WHAT IS THE 2'-8" DIMENSION FOR?. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| D) ENLARGED FLOOR PLAN ON SHEET A6.0 AND ACCESSIBLE |
| SHOWER DETAIL SHOWN ON SAME PAGE DON'T MATCH. SEE |
| LOCATION OF GRAB BARS. REVISE AS REQUIRED TO MATCH. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| DETAILS DON'T MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| E) GRAB BARS LOCATION SHOWN ON FLOOR PLAN DOESN'T |
| COMPLY WITH SEC. 608.3. REVISE AS REQUIRED. |
| |
| RESPONSE: |
| STILL DON'T COMPLY. SEC. 107.2.1 CITY AMENDMENTS. |
| NOTE: TO AVOID CONFLICT/CONFUSION IS BETTER TO |
| COORDINATE WITH PLUMBING REVIEW COMMENTS. |
| |
| ORIGINAL COMMENT: |
| F) SHOWER COMPARTMENT SEAT: SHOW COMPLIANCE WITH THE |
| REQUIREMENTS OF SEC. 610.3 INCLUDING THE CLEARANCE AT |
| THE COMPARTMENT ENTRY, WALL CLEARANCES FOR L SHAPED |
| SEATS AND STRUCTURAL STRENGTH. |
| |
| RESPONSE: |
| STILL DON'T COMPLY. SEC. 107.2.1 CITY AMENDMENTS. |
| NOTE: TO AVOID CONFLICT/CONFUSION IS BETTER TO |
| COORDINATE WITH PLUMBING REVIEW COMMENTS. |
| |
| ORIGINAL COMMENT: |
| 7) SHEET A7.0 DETAIL C IS TAKEN IN THE CONFERENCE ROOM |
| BREAK AREA SINK. THE HEIGHT OF THE CABINET COUNTER TOP |
| IS 36 INCHES FROM THE FLOOR PLUS THE THICKNESS OF THE |
| SINK RIM. PLEASE SHOW COMPLIANCE WITH: |
| |
| 2017 FBC-ACCESS. CODE SECTION 606 LAVATORIES AND SINKS> |
| 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. SAME SHEET SUBMITTED. |
| DETAIL SOWS 2'-10" HEIGHT TO THE TOP OF THE COUNTER. |
| THE RIM OF THE SINK IS HIGHER. THE DIMENSION IS TO BE |
| TAKEN TO THE HIGHER OF THE RIM OR COUNTER SURFACE. |
| REVISE AS REQUIRED. |
| |
| ORIGINAL COMMENT: |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| RESPONSE: |
| THERE IS IS NO RESPONSE LETTER FROM THE ARCHITECT. EVEN |
| THOUGH A RESPONSE LETTER IS NOT MANDATORY IT IS VERY |
| HELPFUL IN EXPEDITING THE REVIEW PROCESS. |
| |
| NEW COMMENTS: |
| ORIGINAL COMMENT: |
| 1- PLANS ARE NOT CLEAR IN SHOWING THE SCOPE OF WORK TO |
| BE DONE TO THE TENANT SPACES AND THEY DON'T SHOW THE |
| NEW WALLS SEPARATING THE TENANTS. EXISTING BUILDING |
| PLAN (SHEET A1.0) AND DEMOLITION PLAN (SHEET A1.1) SHOW |
| WHAT SEEMS TO BE THE PROPOSED TENANT SEPARATION WALL, |
| BUT PLANS DON'T SHOW SCOPE OF WORK. CLEARLY IDENTIFY |
| WHAT IS GOING TO BE DEMOLISHED TO ALLOW FOR NEW TENT |
| SEPARATION WALLS AND PROVIDE DETAILS/SPECIFICATIONS FOR |
| SCOPE OF WORK ON EACH SIDE OF THE TENANT SEPARATION |
| WALLS. |
| NOTE: SEPARATE SUB-PERMITS MAY BE REQUIRED FOR PROPER |
| INSPECTIONS ON BOTH SIDES OF TENANTS. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| RESPONSE: |
| NOT ADDRESSED AT ALL. |
| THERE IS IS NO RESPONSE LETTER FROM THE ARCHITECT. EVEN |
| THOUGH A RESPONSE LETTER IS NOT MANDATORY IT IS VERY |
| HELPFUL IN EXPEDITING THE REVIEW PROCESS. |
| |
| ORIGINAL COMMENT: |
| 2- CLARIFY WHY PROPOSED FLOOR PLAN ON SHEET A2.0 ONLY |
| SHOWS AN ACCESSIBLE COUNTER AT THE CHECK OUT AREA AND |
| NO ONE AT THE CHECK IN AREA. CHECK IN COUNTER AREA IS |
| ALSO USED TO WRITE CHECKS, ETC. SEC. 227.3 |
| FBC-ACCESSIBILITY. |
| |
| RESPONSE: |
| NOT ADDRESSED AT ALL. |
| THERE IS IS NO RESPONSE LETTER FROM THE ARCHITECT. EVEN |
| THOUGH A RESPONSE LETTER IS NOT MANDATORY IT IS VERY |
| HELPFUL IN EXPEDITING THE REVIEW PROCESS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |