Plan Review Notes
Plan Review Notes For Permit 19030897
Permit Number 19030897
Review Stop B
Sequence Number 4
Notes
Date Text
2019-06-17 16:33:23 
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19030897
 ADD: 1411 N. FLAGLER DRIVE SUITE 8900
 CONT: LEIGHTON MCGINN
 TEL: 561863-4455
 E-MAIL: [email protected]
  
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 4TH REVIEW
 DATE: 06/17/19
 ACTION: DENIED
  
 ORIGINAL COMMENT:
 1) THE COVERSHEET UNDER APPLICABLE CODES LIST THE
 BUILDING TYPE AS A TYPE V(A) UNSPRINKLERED. PLEASE
 REVIEW THE BUILDING AND SITE. THE VICTOR FARRIS
 BUILDING IS A 9 STORY HIGHRISE, FULLY SPRINKLERED.
 PLEASE UPDATE THE PLANS TO THE CORRECT BUILDING TYPE.
 SEE THE 2017 FBC-B TABLE 504.4.
  
 RESPONSE:
 REPEAT COMMENT. FOUR TIMES. PLANS SUBMITTED SHOW SAME
 INFORMATION FROM LAST BUILDING REVIEW.
 BUILDING TYPE WAS REVISED TO TYPE II(A)SPRINKLERED.
 THIS IS INCORRECT AGAIN. ACCORDING TO TABLE 504.4
 FBC-BUILDING THE MAXIMUM NUMBER OF STORIES ABOVE GRADE
 PLANE ALLOWED FOR TYPE II(A) SPRINKLERED BUILDING FOR A
 BUSINESS OCCUPANCY IS 6 STORIES. SEE TABLE 504.4 AND
 REVISE AS REQUIRED.
  
  
 2)OK.
  
 3)OK.
  
 4) OK.
  
 5) LIFE SAFETY SHEET:
  
 5A)OK.
  
 5B)OK.
  
 ORIGINAL COMMENT:
 5C) THE OTHER ISSUE WITH THE RECEPTION/ CONFERENCE ROOM
 OCCUPANT LOAD IS THE COMMON PATH OF TRAVEL.
 SEE TABLE 1006.2.1 THE MAXIMUM OCCUPANT LOAD OF 30
 OCCUPANTS IN THE ASSEMBLY OCCUPANCY THE COMMON PATH OF
 TRAVEL IS LIMITED TO 75 FEET AND THE MAXIMUM OCCUPANT
 LOAD OF 49, TABLE 1006.1.2.
  
 PLEASE REVIEW SECTION 1006.2.1 EGRESS BASED ON OCCUPANT
 LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE. TWO
 EXITS OR EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE
 PROVIDED WHERE THE DESIGN OCCUPANT LOAD OR THE COMMON
 PATH OF EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES
 LISTED IN TABLE 1006.2.1. THE EXCEPTION FORI-2 DOES NOT
 WORK SINCE THIS IS NOT A CARE SUITE WITHIN A HOSPITAL.
 PLEASE PROVIDE 2 EXIT ACCESS DOORWAY THAT WILL BE IN
 COMPLIANCE WITH FBC-B 1007.1.1 EXCEPTION2.
 FBC-B 1007.1.1 EXCEPTION2. WHERE A BUILDING IS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2, THE
 SEPARATION DISTANCE SHALL BE NOT LESS THAN ONE-THIRD OF
 THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF
 THE AREA SERVED.
  
 THERE ARE 2 AREAS OF CONCERN, 1ST IN THE CONFERENCE
 ROOM ITSELF REQUIRING 2 MEANS OF EGRESS, OUTSWING DOOR
 REQUIRED. THE 2ND AREA IS WITHIN THE TENANT SPACE
 ITSELF THE TOTAL OCCUPANT LOAD IS OVER 49 REQUIRING
 ALSO 2 MEANS OF EGRESS.
  
 RESPONSE:
 REPEAT COMMENT. FOUR TIMES. (ARCHITECT TO SEE FLORIDA
 STATUTE 553.80(2)(B)). FEES WILL APPLY.
  
 TENANT SPACE PROPOSED SECOND MEANS OF EGRESS DOESN'T
 COMPLY WITH EXCEPTION #2 OF SEC. 1007.1.1 FBC-BUILDING.
 THE SEPARATION DISTANCE SHALL BE NOT LESS THAN
 ONE-THIRD OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE AREA SERVED. THE DIAGONAL DISTANCE
 SHOWN IS 95'-0". ONE THIRD 1/3 OF 95'-0" IS 31'-8". THE
 DISTANCE BETWEEN THE TWO EXITS IS +/- 22'-0".
 THEREFORE, IT DOESN'T COMPLY. REVISE AS REQUIRED.
 NOTE: THE DISTANCE IS MEASURED THE SAME WAY THE
 DIAGONAL DIMENSION IS DIMENSIONED. IS THE DISTANCE
 BETWEEN THE TWO DOORS NOT THE TRAVEL DISTANCE BETWEEN
 THE TWO DOORS AS SHOWN ON PLAN. REVISE AS REQUIRED.
 ALSO, PLEASE CLEAN UP INFORMATION ON PLANS. THERE ARE
 SOME DIMENSIONS THAT CORRESPOND TO PREVIOUS PLANS THAT
 NO LONGER APPLIES. FOR EXAMPLE, SEE THE TRAVEL DISTANCE
 95'-0" SHOWN BY THE CONFERENCE ROOM AND TOTAL TRAVEL
 DISTANCE SHOWN BY THE ENTRY DOOR. PLEASE MAKE SURE ALL
 REVISED FLOOR PLANS MATCH. OFFICE LAYOUT SHOWN BY THE
 SECOND PROPOSED EXIT DOESN'T MATCH.
  
 NOTE: SCALE SHOWN ON SHEET A2.0 AND A3.0 IS INCORRECT.
 REVISE AS REQUIRED.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 6) SHEET A6.0 ACCESSIBLE FEATURES:
  
 THE FOLLOWING COMMENTS APPLY TO THE SHOWER COMPARTMENT
 BASED ON REVISIONS DONE TO ADDRESSEES ORIGINAL COMMENTS
 REGARDING ACCESSIBLE FEATURES.
  
 SHOWER COMPARTMENT (SEC. 608 FBC-ACCESSIBILITY):
 A)OK.
  
 B) OK.
  
 ORIGINAL COMMENT:
 C) IT IS NOT CLEAR WHAT IS THE 2'-8" DIMENSION SHOWN BY
 THE SHOWER AREA. IS THERE A PARTITION BETWEEN THE WATER
 CLOSET AND THE SHOWER?. SEC. 107.2.1 CITY AMENDMENTS
 AND SEC. 608.2.2.1
  
 RESPONSE:
 STILL NO CLEAR WHAT IS THE 2'-8" DIMENSION FOR?. SEC.
 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 D) ENLARGED FLOOR PLAN ON SHEET A6.0 AND ACCESSIBLE
 SHOWER DETAIL SHOWN ON SAME PAGE DON'T MATCH. SEE
 LOCATION OF GRAB BARS. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 DETAILS DON'T MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 E) GRAB BARS LOCATION SHOWN ON FLOOR PLAN DOESN'T
 COMPLY WITH SEC. 608.3. REVISE AS REQUIRED.
  
 RESPONSE:
 STILL DON'T COMPLY. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: TO AVOID CONFLICT/CONFUSION IS BETTER TO
 COORDINATE WITH PLUMBING REVIEW COMMENTS.
  
 ORIGINAL COMMENT:
 F) SHOWER COMPARTMENT SEAT: SHOW COMPLIANCE WITH THE
 REQUIREMENTS OF SEC. 610.3 INCLUDING THE CLEARANCE AT
 THE COMPARTMENT ENTRY, WALL CLEARANCES FOR L SHAPED
 SEATS AND STRUCTURAL STRENGTH.
  
 RESPONSE:
 STILL DON'T COMPLY. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: TO AVOID CONFLICT/CONFUSION IS BETTER TO
 COORDINATE WITH PLUMBING REVIEW COMMENTS.
  
 ORIGINAL COMMENT:
 7) SHEET A7.0 DETAIL C IS TAKEN IN THE CONFERENCE ROOM
 BREAK AREA SINK. THE HEIGHT OF THE CABINET COUNTER TOP
 IS 36 INCHES FROM THE FLOOR PLUS THE THICKNESS OF THE
 SINK RIM. PLEASE SHOW COMPLIANCE WITH:
  
 2017 FBC-ACCESS. CODE SECTION 606 LAVATORIES AND SINKS>
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. SAME SHEET SUBMITTED.
 DETAIL SOWS 2'-10" HEIGHT TO THE TOP OF THE COUNTER.
 THE RIM OF THE SINK IS HIGHER. THE DIMENSION IS TO BE
 TAKEN TO THE HIGHER OF THE RIM OR COUNTER SURFACE.
 REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 RESPONSE:
 THERE IS IS NO RESPONSE LETTER FROM THE ARCHITECT. EVEN
 THOUGH A RESPONSE LETTER IS NOT MANDATORY IT IS VERY
 HELPFUL IN EXPEDITING THE REVIEW PROCESS.
  
 NEW COMMENTS:
 ORIGINAL COMMENT:
 1- PLANS ARE NOT CLEAR IN SHOWING THE SCOPE OF WORK TO
 BE DONE TO THE TENANT SPACES AND THEY DON'T SHOW THE
 NEW WALLS SEPARATING THE TENANTS. EXISTING BUILDING
 PLAN (SHEET A1.0) AND DEMOLITION PLAN (SHEET A1.1) SHOW
 WHAT SEEMS TO BE THE PROPOSED TENANT SEPARATION WALL,
 BUT PLANS DON'T SHOW SCOPE OF WORK. CLEARLY IDENTIFY
 WHAT IS GOING TO BE DEMOLISHED TO ALLOW FOR NEW TENT
 SEPARATION WALLS AND PROVIDE DETAILS/SPECIFICATIONS FOR
 SCOPE OF WORK ON EACH SIDE OF THE TENANT SEPARATION
 WALLS.
 NOTE: SEPARATE SUB-PERMITS MAY BE REQUIRED FOR PROPER
 INSPECTIONS ON BOTH SIDES OF TENANTS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED AT ALL.
 THERE IS IS NO RESPONSE LETTER FROM THE ARCHITECT. EVEN
 THOUGH A RESPONSE LETTER IS NOT MANDATORY IT IS VERY
 HELPFUL IN EXPEDITING THE REVIEW PROCESS.
  
 ORIGINAL COMMENT:
 2- CLARIFY WHY PROPOSED FLOOR PLAN ON SHEET A2.0 ONLY
 SHOWS AN ACCESSIBLE COUNTER AT THE CHECK OUT AREA AND
 NO ONE AT THE CHECK IN AREA. CHECK IN COUNTER AREA IS
 ALSO USED TO WRITE CHECKS, ETC. SEC. 227.3
 FBC-ACCESSIBILITY.
  
 RESPONSE:
 NOT ADDRESSED AT ALL.
 THERE IS IS NO RESPONSE LETTER FROM THE ARCHITECT. EVEN
 THOUGH A RESPONSE LETTER IS NOT MANDATORY IT IS VERY
 HELPFUL IN EXPEDITING THE REVIEW PROCESS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved