Plan Review Notes
Plan Review Notes For Permit 19030897
Permit Number 19030897
Review Stop P
Sequence Number 3
Notes
Date Text
2019-05-28 14:32:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 3RD REVIEW
 PLUMBING COMMEMTS: DENIED
 PLEASE NOTE THAT PLUMBING WILL NOT BE APPROVED UNTIL
 THE ISSUES ON THE ARCHITECTURAL PLANS HAVE BEEN
 CORRECTLY ADDRESSED
  
 1. 3RD REQUEST- ARCHITECTURAL ISSUE: PLAN SHEET A6.0;
 THE LOCATION OF THE REAR GRAB BAR SHALL COMPLY WITH
 FBC-ACCESS. SEC.604.5.2. 24" OPPOSITE THE 12" NOT SHOWN
 ON DETAIL (GRAB BAR AT WATER CLOSET) SHT. A6.0. TO
 CLARIFY THE DETAIL, DIMENSION FROM CENTER OF WATER
 CLOSET TO LEFT SHALL BE 24? MIN., NOT 12?.
  
 2. 3RD REQUEST-PLAN SHEET P-2: PLUMBING GENERAL NOTE #1
 REFERS TO THE 2014 FBC. THE CODE IN EFFECT IS THE 2017
 FBC. REVISE AND RESUBMIT.
  
 3. 3RD REQUEST-PER WPB FBC 107.2.1, SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE TANKLESS WATER
 HEATERS.
  
 4. 2ND REQUEST- ARCHITECTURAL ISSUE: SHT. A6.0 DETAIL
 #9 SHOWS GRAB BARS MEASURED TO THE ESCUTCHEON RING; THE
 DETAIL FOR THE GRAB BARS AT WATER CLOSET SHOWS MEASURED
 TO THE CENTER OF THE GRAB BAR, THEY BOTH SHALL SHOW
 MEASURED TO THE TOP OF THE GRIPPING SURFACE. FBC ACC
 609.4. PLEASE NOTE THAT DETAIL #7 BATHROOM BACKING
 DETAIL CORRECTLY SHOWS THE REQUIREMENTS. RECONCILE
 DETAIL #9 WITH #7.
  
 5. REGARDING THE FOLLOWING COMMENTS MADE DURING THE
 SECOND REVIEW CONCERNING THE SHOWER IN THE TOILET RM W/
 SHOWER STAFF RM #110, PLEASE NOTE:
 A. ARCHITECTURAL ISSUE: SHT. A6.0 DETAIL #5 THE
 ACCESSIBLE SHOWER DETAIL DOES NOT MATCH DETAIL #1
 ENLARGED BATHROOM THE SHOWER SHALL COMPLY WITH FBC ACC
 608.2.2.1, 608.3.2 , 608.5.2. NOTE THAT THE SPACE AND
 CONFIGURATION ALLOWED BY THE ARCHITECT DOES NOT MEET
 THE REQUIREMENTS FOR A STANDARD ROLL IN SHOWER
 COMPARTMENT.
 B. ARCHITECTURAL ISSUE: THE SEAT IS BEING SHOWN ON THE
 SAME SIDE AS THE END GRAB BAR IT SHALL BE ON THE
 OPPOSITE END IT WILL BE DIFFICULT TO COMPLY WITH THE
 ANGLE WALL. FBC ACC 608.3.2
 C. ARCHITECTURAL ISSUE: THE ENDS OF THE GRAB BARS SHALL
 BE 6" MAX FROM ADJACENT WALL. FBC ACC 608.3.2
 D. ARCHITECTURAL ISSUE: SHOW CLEAR FLOW SPACE FOR
 SHOWER. FBC ACC 608.2.2.1
  
 6. ADDITIONAL COMMENTS CONCERNING TOILET RM W/ SHOWER
 STAFF RM #110:
 A. ARCHITECTURAL ISSUE: FBC ACC 604.2 REQUIRES THAT THE
 WATER CLOSET POSITIONED WITH A WALL OR PARTITION TO THE
 REAR AND ONE SIDE OF THE FIXTURE; SIDE AND REAR HAND
 BARS SHALL CONFORM TO FBC ACC 604.5.1 AND 605.2. A
 PULLDOWN GRAB BAR IS NOT COMPLIANT AND SHALL NOT BE
 USED.
 B. ARCHITECTURAL ISSUE: FBC ACC 604.7 REQUIRES TOILET
 PAPER DISPENSER TO BE LOCATED ON THE SIDE WALL 7?-9?
 FRONT OF THE WATER CLOSET TO CENTER OF DISPENSER AND
 INSIDE THE SPACE OF 15? MINIMUM TO 48? MAXIMUM ABOVE
 THE FLOOR.
 C. ARCHITECTURAL ISSUE: NOTE THAT PER 604.8.1.2, THE
 ENTRY DOOR SHALL BE LOCATED IN THE FRONT PARTITION OR
 IN THE SIDE WALL OR PARTITION FARTHEST FROM THE WATER
 CLOSET. WHERE LOCATED IN THE FRONT PARTITION, THE DOOR
 OPENING SHALL BE 4 INCHES (100 MM) MAXIMUM FROM THE
 SIDE WALL OR PARTITION FARTHEST FROM THE WATER CLOSET.
 WHERE LOCATED IN THE SIDE WALL OR PARTITION, THE DOOR
 OPENING SHALL BE 4 INCHES (100 MM) MAXIMUM FROM THE
 FRONT PARTITION.
  
 7. NEW COMMENTS
 A. PLAN SHEET P-1 AND P-3; MOP SINK LOCATION. RECONCILE
 SANITARY ISOMETRIC ON P-3 WITH THE FLOOR PLAN ON P-1.
 B. REGARDING THE FOLLOWING ORIGINAL COMMENT: ?TEMPERED
 WATER IS REQUIRED AT THE LAVATORIES IN THE TOILET ROOMS
 AND BATHROOM PER FBC-PLUMBING. SEC. 416.5. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.? PER WPB FBC 107.2.1, PROVIDE CUT
 SHEET AND SPEC FOR OWNER FURNISHED WALL MOUNTED, ADA
 COMPLIANT ANTI-SCALD VALVE SHOWING COMPLIANCE WITH ASSE
 1070 OR CSA B125.3 AS REQUIRED BY FBC PL 416.5 FOR THE
 HANDICAPPED LAVATORIES. ALSO PROVIDE A DETAIL OF
 INSTALLATION TO SHOW COMPLIANCE WITH FBC ACC 309.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19030897 1411 N FLAGLER DR # 8900