2019-05-06 15:25:53 | |
| 2ND REVIEW: 19030897 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PREVIOUS COMMENTS NOT COMPLIED IT APPEARS THAT PLUMBING |
| PAGES WERE NOT REVISED THE RESPONSE LETTER REFERRED TO |
| MEP LETTER IT WAS NOT IN PERMIT DOCUMENT PACKAGE. |
| |
| 10) THE LOCATION OF THE REAR GRAB BAR SHALL COMPLY WITH |
| FBC-ACCESS. SEC.604.5.2. 24" OPPOSITE THE 12" NOT SHOWN |
| ON DETAIL SHT. A6.0 |
| 13) SHT. A7.1 - THE MAXIMUM HEIGHT OF THE KITCHEN |
| CABINETS ( DETAIL "D") SHALL BE 34 INCHES ABOVE THE |
| FINISH FLOOR. FBC-ACCESS. SEC. 606.3. |
| 14) A MOP SINK IS REQUIRED PER 2017 FBC-PLUMBING TABLE |
| 403.1. NOT SHOWN ON PLUMBING PLAN. |
| 15) THE SINK IN EXAM ROOM #1 IS NOT SHOWN ON THE |
| SANITARY OR WATER RISER DIAGRAM. CLARIFY. |
| 16) SHOW THE LOCATION OF THE DRINKING FOUNTAINS ON SHT. |
| A2.0. DRINKING FOUNTAINS SHALL COMPLY WITH FBC-ACCESS. |
| SEC.307 FOR PROTRUDING OBJECTS. |
| 17) THE LAYOUT OF EXAM ROOM #7 ON SHT. A2.0 DOES NOT |
| CORRELATE WITH THE LAYOUT ON SHT. P-1. CLARIFY. |
| 18) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN THE |
| TOILET ROOMS AND BATHROOM PER FBC-PLUMBING. SEC. |
| 416.5.TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. |
| 19) SHT. P-2, GENERAL NOTE #1 REFERS TO THE 2014 FBC. |
| THE CODE IN EFFECT IS THE 2017 FBC. |
| 20) SHT. P-2 - PLUMBING FIXTURE CONNECTION SCHEDULE - |
| NOTE #2 REFERS TO ORDINANCE 8.31 OF MIAMI DADE COUNTY. |
| REMOVE THIS NOTE FROM THE PLAN. NOTE #3 REFERS TO THE |
| RESIDENTIAL PLUMBING CODE. REMOVE THIS NOTE FROM THE |
| PLANS. |
| 21) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| TANKLESS WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| NEW COMMENTS: |
| |
| 1. SHT. A6.0 DETAIL #5 THE ACCESSIBLE SHOWER DETAIL |
| DOES NOT MATCH DETAIL #1 ENLARGED BATHROOM THE SHOWER |
| SHALL COMPLY WITH FBC ACC 608.2.2.1, 608.3.2 , 608.5.2 |
| THE SEAT IS BEING SHOWN ON THE SAME SIDE AS THE END |
| GRAB BAR IT SHALL BE ON THE APOSTATE END IT WILL BE |
| DIFFICULT TO COMPLY WITH THE ANGLE WALL. FBC ACC |
| 608.3.2 |
| THE ENDS OF THE GRAB BARS SHALL BE 6" MAX FROM ADJACENT |
| WALL. FBC ACC 608.3.2 |
| SHOW CLEAR FLOW SPACE FOR SHOWER.FBC ACC 608.2.2.1 |
| |
| 2. SHT. A6.0 DETAIL #9 SHOWS GRAB BARS MEASURED TO THE |
| THE ESCUTCHEON RING THE DETAIL FOR THE GRAB BARS AT |
| WATER CLOSET SHOWS MEASURED TO THE CENTER OF THE GRAB |
| BAR, THEY BOTH SHALL SHOW MEASURED TO THE TOP OF THE |
| GRIPPING SURFACE. FBC ACC 609.4 |
| |
| 3. A6.0 PROVIDE DETAIL FOR PULL DOWN GRAB BAR AND SHOW |
| ON SHOW ON ACCESSORY SCHEDULE. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 4. MOP SINK AND WATER FOUNTAIN ARE NOT SHOWN ON THE |
| PLUMBING PAGES THEY ARE SHOWN ARCHITECTURAL PAGES |
| PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 5. THE FLOOR PLAN ON SHT A2.0 IS SHOWING A CORRIDOR |
| ALONG SIDE BATHROOM 110 A CLOSET 103 THIS IS NOT SHOWN |
| ON THE MEP PAGES AT THE END OF THE CORRIDOR IS THE |
| REQUIRED WATER FOUNTAIN. PLEASE CLARIFY. PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |