Plan Review Notes
Plan Review Notes For Permit 19030897
Permit Number 19030897
Review Stop B
Sequence Number 1
Notes
Date Text
2019-03-27 07:59:542017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19030897
 ADD: 1411 N. FLAGLER DRIVE SUITE 8900
 CONT: LEIGHTON MCGINN
 TEL: 561863-4455
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 26/ 2019
 ACTION: DENIED
  
 1) THE COVERSHEET UNDER APPLICABLE CODES LIST THE
 BUILDING TYPE AS A TYPE V(A) UNSPRINKLERED. PLEASE
 REVIEW THE BUILDING AND SITE. THE VICTOR FARRIS
 BUILDING IS A 9 STORY HIGHRISE, FULLY SPRINKLERED.
 PLEASE UPDATE THE PLANS TO THE CORRECT BUILDING TYPE.
 SEE THE 2017 FBC-B TABLE 504.4.
  
 2) THE COVERSHEET UNDER THE HEADING OF GENERAL NOTE 10
 INDICATES FIRE RETARDANT TREATED AS PER THE REQUIREMENT
 OF THE 2017 FBC-RESIDENTIAL CODE. PLEASE REMOVE THIS
 NOTE SINCE IT HAS NOTHING TO DO WITH THIS REVIEW, THIS
 IS A COMMERCIAL HIGH-RISE. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) SHEET A2.0 HAS (2) NOTES THAT DEAL WITH THE
 RESIDENTIAL CODE FBC-R 308. PLEASE REMOVE ALL NOTES
 DEALING WITH THE ONE & TWO FAMILY RESIDENTIAL CODE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 4) SHEET A2.0 ALSO HAS NOTES REFERRING TO THE FEDERAL
 A.D.A. AND THE STATE OF FLORIDA ACCESSIBILITY CODE.
 THEN LIST VARIOUS CODE SECTIONS 4.1.6, 4.1.9, 4.13.6AND
 ALL OF THE S. F. B. C. (SOUTH FLORIDA BUILDING CODE).
  
 4A) SECTIONS 4.1.6, 4.1.9, 4.13.6 ARE OUT OF THE ADA,
 NOT THE FLORIDA ACCESSIBILITY CODE. SECTIONS 4.1.6 &
 4.1.9 ARE MENTIONED A SECOND TIME. PLEASE IF
 REFERENCING THE 2017 FBC-ACCESS. CODE PLEASE USE THE
 CORRECT CODE SECTIONS, NOT THE ADA.
  
 4B) THE S. F. B. C. (SOUTH FLORIDA BUILDING CODE) ARE
 NO LONGER A CURRENT CODE. YOU ONLY REFER TO THE HIGH
 VELOCITY HURRICANE ZONE WHEN WORKING IN EITHER DADE OR
 BROWARD COUNTIES. SEE THE 2017 FBC-B DEFINITIONS
 CHAPTER 2. HIGH VELOCITY HURRICANE ZONE. THIS ZONE
 CONSISTS OF BROWARD AND DADE COUNTIES.
  
 5) LIFE SAFETY SHEET:
  
 5A) THE OCCUPANCY LOAD CLASSIFICATION CHART NEEDS TO BE
 REVIEWED FOR CODE COMPLIANCE. THE OFFICE AND EXAM
 ROOMS? NEED BOTH TO BE FIGURED AT 100 SQ. FT. /PER
 OCCUPANT, NOT THE 240 GROSS FOR THE EXAM ROOMS.
 PLEASE REVIEW IN THE 2017 FBC-B TABLE 1004.1.2. THE 240
 GROSS IS USED IN INSTITUTIONAL AREAS SUCH AS INPATIENT
 TREATMENT AREAS NOT IN A BUSINESS OCCUPANCY. SO THE
 TOTAL AREA OF THE BUSINESS PORTION OF THE TENANT SPACE
 IS 2407 SQ. FT. OR 25 OCCUPANTS, YOU ALWAYS ROUND UP,
 YOU NEVER HAVE PARTIAL OCCUPANTS, SEE BOAF INFORMAL
 INTERPRETATIONS.
  
 5B) THE RECEPTION AREA SHOULD READ RECEPTION &
 CONFERENCE ROOM, THE SQUARE FOOTAGE OF 1,038/ 15= 95
 WHEN ROUNDED UP. PLEASE UPDATE PLANS, 2017 FBC-B TABLE
 1004.1.2.
  
 5C) THE OTHER ISSUE WITH THE RECEPTION/ CONFERENCE ROOM
 OCCUPANT LOAD IS THE COMMON PATH OF TRAVEL.
 SEE TABLE 1006.2.1 THE MAXIMUM OCCUPANT LOAD OF 30
 OCCUPANTS IN THE ASSEMBLY OCCUPANCY THE COMMON PATH OF
 TRAVEL IS LIMITED TO 75 FEET AND THE MAXIMUM OCCUPANT
 LOAD OF 49, TABLE 1006.1.2.
  
 PLEASE REVIEW SECTION 1006.2.1 EGRESS BASED ON OCCUPANT
 LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE. TWO
 EXITS OR EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE
 PROVIDED WHERE THE DESIGN OCCUPANT LOAD OR THE COMMON
 PATH OF EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES
 LISTED IN TABLE 1006.2.1. THE EXCEPTION FORI-2 DOES NOT
 WORK SINCE THIS IS NOT A CARE SUITE WITHIN A HOSPITAL.
 PLEASE PROVIDE 2 EXIT ACCESS DOORWAY THAT WILL BE IN
 COMPLIANCE WITH FBC-B 1007.1.1 EXCEPTION2.
 FBC-B 1007.1.1 EXCEPTION2. WHERE A BUILDING IS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2, THE
 SEPARATION DISTANCE SHALL BE NOT LESS THAN ONE-THIRD OF
 THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF
 THE AREA SERVED.
  
 THERE ARE 2 AREAS OF CONCERN, 1ST IN THE CONFERENCE
 ROOM ITSELF REQUIRING 2 MEANS OF EGRESS, OUTSWING DOOR
 REQUIRED. THE 2ND AREA IS WITHIN THE TENANT SPACE
 ITSELF THE TOTAL OCCUPANT LOAD IS OVER 49 REQUIRING
 ALSO 2 MEANS OF EGRESS.
  
 6) SHEET A6.0 ACCESSIBLE FEATURES:
  
 6A) THE PLAN SHOWS AN ACCESSIBLE RESTROOM & BATHROOM
 WITHIN THE RESTROOM & BATHROOM THE PLAN FAILS TO SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY SECTION
 604.3.1 CLEARANCE/ SIZE. 604.3.1 SIZE. CLEARANCE AROUND
 A WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
  
 6B) THE PLAN ALSO SHOWS WHAT APPEARS TO BE AN
 ACCESSIBLE BATHROOM EQUIPPED WITH A WALK-IN SHOWER.
 PLEASE NOTE THIS BATHROOM HAS TO MEET ALL OF THE
 REQUIREMENTS FOR AN ACCESSIBLE RESTROOM, IT DOES NOT
 MEET THE REQUIREMENT FOR A PRIVATE BATHROOM.
 FBC-ACCESS. CODE 603.2.3 EXCEPT. 1 DOORS TO A TOILET
 ROOM OR BATHING ROOM FOR A SINGLE OCCUPANT ACCESSED
 ONLY THROUGH A PRIVATE OFFICE AND NOT FOR COMMON USE OR
 PUBLIC USE SHALL BE PERMITTED TO SWING INTO THE CLEAR
 FLOOR SPACE OR CLEARANCE PROVIDED THE SWING OF THE DOOR
 CAN BE REVERSED TO COMPLY WITH 603.2.3.
  
 6C) THE BATHROOM SHOWS A SHOWER BUT DOES NOT SHOW ANY
 DETAILS OF GRAB BARS, BACKING, OR THE WALL OF WHICH
 WHERE THE CONTROLS ARE INSTALLED, CLEAR FLOOR SPACE,
 NOTHING. 609.4, 608.5.2, & 608.2.2.
  
 6D) THE BATHROOM ALSO SHOWS THE INSWING DOOR SWINGING
 INTO THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND SHOWER. PLEASE NOTE NEITHER THE CLEAR FLOOR
 SPACE FOR THE SHOWER AND WATER CLOSET IS SHOWN.
 107.2.1.2 ADDITIONAL INFORMATION REQUIRED. 604.3.1 &
 604.3.2 OVERLAP.
  
 6E) PLEASE REVIEW DETAIL # 6 SINKS FOR HEIGHT
 REQUIREMENTS. THIS DETAIL SHOWS THE HEIGHT OF 2 FOOT 10
 INCHES TAKEN FROM THE FLOOR TO THE COUNTER TOP. THE
 CODE READS LAVATORIES AND SINKS SHALL BE INSTALLED WITH
 THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. THE HIGHER OF THE 2 SURFACES, DEPENDING ON THE
 FLANGE HEIGHT OF THE SINK YOU MAYBE OVER CONSTRUCTION
 TOLERANCES. 606 LAVATORIES AND SINKS> 2017
 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
  
 7) SHEET A7.0 DETAIL C IS TAKEN IN THE CONFERENCE ROOM
 BREAK AREA SINK. THE HEIGHT OF THE CABINET COUNTERTOP
 IS 36 INCHES FROM THE FLOOR PLUS THE THICKNESS OF THE
 SINK RIM. PLEASE SHOW COMPLIANCE WITH:
  
 2017 FBC-ACCESS. CODE SECTION 606 LAVATORIES AND SINKS>
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved