2019-03-19 14:47:02 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 19030873 (17120971 MASTER) |
| REVIEWED: MARCH 19, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,5TH EDITION (2014) |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| |
| 1) 1503.4 FBC[B] ROOF DRAINAGE PROVIDE ROOF DRAIN |
| CALCULATIONS AND DESIGN TO COMPLY WITH SECTIONS 1106 |
| AND 1107, AS APPLICABLE, OF THE FLORIDA BUILDING CODE, |
| PLUMBING, CHAPTER 11. |
| -PLEASE PROVIDE ROOF DRAINAGE CALCULATIONS, OR |
| INDICATE WHICH PAGE THEY ARE LOCATED ON IN MASTER |
| PERMIT. I DIDN?T SEE DRAINAGE CALCULATIONS IN MASTER |
| PERMIT # 17120971 ON ROOF OR PLUMBING PLANS. |
| |
| 2) [RAS 117]PROVIDE ENGINEERING FOR ENHANCED NAILING AS |
| STATED IN PRODUCT APPROVAL 17-1003.08 UNDER GENERAL |
| LIMITATIONS #7. |
| -PROVIDE ENGINEERING FOR ANY SECTION OF ROOF THAT HAS |
| MECHANICALLY ATTACHED BASE SHEET. |
| 1508.1 FBC[B] ALSO, PROVIDE ATTACHMENT FOR ANY |
| INSULATION INSTALLED ABOVE ROOF DECK AS STATED IN |
| GENERAL LIMITATION #5. |
| |
| 3) 1609.1.1 FBC[B] DETERMINATION OF WIND LOADS. WIND |
| LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE |
| DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF ASCE |
| 7 OR PROVISIONS OF THE ALTERNATE ALL-HEIGHTS METHOD IN |
| SECTION 1609.6. |
| -PROVIDE DESIGN PRESSURES FOR THE OPENINGS BASED ON |
| EXPOSURE C. |
| |
| 4) 1609.1.2 FBC[B] PROTECTION OF OPENINGS. IN |
| WIND-BORNE DEBRIS REGIONS, GLAZED OPENINGS IN BUILDINGS |
| SHALL BE IMPACT RESISTANT OR PROTECTED WITH AN |
| IMPACT-RESISTANT COVERING MEETING THE REQUIREMENTS OF |
| ANSI/DASMA 115 |
| -THE SOLAR TUBE SELECTED ON PRODUCT APPROVAL IS |
| NON-IMPACT RATED. PLEASE SELECT AN IMPACT RATED SOLAR |
| TUBE. |
| |
| |
| NOTES: |
| |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |