Plan Review Notes
Plan Review Notes For Permit 19030873
Permit Number 19030873
Review Stop B
Sequence Number 1
Notes
Date Text
2019-03-19 14:47:02****CORRECTIONS****
 W.P.B. PERMIT: 19030873 (17120971 MASTER)
 REVIEWED: MARCH 19, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,5TH EDITION (2014)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
  
 1) 1503.4 FBC[B] ROOF DRAINAGE PROVIDE ROOF DRAIN
 CALCULATIONS AND DESIGN TO COMPLY WITH SECTIONS 1106
 AND 1107, AS APPLICABLE, OF THE FLORIDA BUILDING CODE,
 PLUMBING, CHAPTER 11.
  -PLEASE PROVIDE ROOF DRAINAGE CALCULATIONS, OR
 INDICATE WHICH PAGE THEY ARE LOCATED ON IN MASTER
 PERMIT. I DIDN?T SEE DRAINAGE CALCULATIONS IN MASTER
 PERMIT # 17120971 ON ROOF OR PLUMBING PLANS.
  
 2) [RAS 117]PROVIDE ENGINEERING FOR ENHANCED NAILING AS
 STATED IN PRODUCT APPROVAL 17-1003.08 UNDER GENERAL
 LIMITATIONS #7.
  -PROVIDE ENGINEERING FOR ANY SECTION OF ROOF THAT HAS
 MECHANICALLY ATTACHED BASE SHEET.
 1508.1 FBC[B] ALSO, PROVIDE ATTACHMENT FOR ANY
 INSULATION INSTALLED ABOVE ROOF DECK AS STATED IN
 GENERAL LIMITATION #5.
  
 3) 1609.1.1 FBC[B] DETERMINATION OF WIND LOADS. WIND
 LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF ASCE
 7 OR PROVISIONS OF THE ALTERNATE ALL-HEIGHTS METHOD IN
 SECTION 1609.6.
  -PROVIDE DESIGN PRESSURES FOR THE OPENINGS BASED ON
 EXPOSURE C.
  
 4) 1609.1.2 FBC[B] PROTECTION OF OPENINGS. IN
 WIND-BORNE DEBRIS REGIONS, GLAZED OPENINGS IN BUILDINGS
 SHALL BE IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT-RESISTANT COVERING MEETING THE REQUIREMENTS OF
 ANSI/DASMA 115
 -THE SOLAR TUBE SELECTED ON PRODUCT APPROVAL IS
 NON-IMPACT RATED. PLEASE SELECT AN IMPACT RATED SOLAR
 TUBE.
  
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  