2019-03-20 06:42:37 | PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE |
| REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL |
| PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE |
| RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1) VALUE OF JOB SEEMS LOW. PLEASE PROVIDE A SIGNED |
| CONTRACT FOR THIS JOB.109.3 BUILDING PERMIT VALUATIONS. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATIONOF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT |
| SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW |
| DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL |
| OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| |
| 2) PERSON DRAWING PLANS SHALL SIGN AND DATE.FBC 107.1 |
| |
| 3) AAV WOULD NOT BE PERMITTED AS THIS IS A SEPERATE |
| BUILDING DRAIN CONNECTING TO THE SEWER. PER FBC-P 904.1 |
| THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL HAVE |
| NOT LESS THEN ONE VENT PIPIE THAT EXTEND TO THE |
| OUTDOORS. |
| |
| 4) PLANS DO NOT INDICATE IF THESE SINKS ARE NEW OR |
| EXISTING. WHERE IS THE HOT AND COLD WATER COMING FROM? |
| FBC 107.1 |
| |
| |