Plan Review Notes
Plan Review Notes For Permit 19030800
Permit Number 19030800
Review Stop G
Sequence Number 2
Notes
Date Text
2019-04-25 10:54:01GAS 2ND REVIEW**DENIED** 2ND REQUEST ON ALL COMMENTS**I
 WOULD RECOMMEND YOU COMING IN FOR A REVIEW OF YOUR
 PLANS BEFORE RE-SUBMITTAL
  
 **PLEASE NOTE FL ST 553.80 (B)2B WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) NOT ADDRESSED. PROVIDE MATERIAL AND PIPE SIZE
 LEAVING THE GAS METER THAT YOU ARE CONNECTING
 INTO.SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
 2) ANSWERED.
  
 3) NOT ADDRESSED. CITY RECORDS SHOW THIS EXISTING
 SYSTEM AS 12" W.C AND NOT 2PSI AS YOU CALL OUT. PLEASE
 CLARIFY IS IT YOUR INTEND TO UPGRADE THE GAS METER AND
 INSTALL PRESSURE REGS FOR ALL OTHER APPLIANCES? FBC-R G
 2413.2, 2413.4.3
  
 4) PROVIDE A COMPLETE AND ACCURATE GAS ISOMETRIC
 DRAWING. FBC 107.3.5
  
 5) YOU SUBMITTED DOCUMENTS CONFLICT WITH EACH OTHER.
 ONE SHEET CALL OUT 330,000 BTU'S @ 15' P.E PIPING , THE
 NEXT PAGE CALLS OUT 350,000 BTU'S @ 15' P.E. PLEASE
 CLARIFY AND REMOVE ALL PAGES THAT ARE NOT PART OF THE
 DESIGN. FBC 107.2.1
  
 6) NEW COMMENT: IF 2LB SYSTEM. AT SOME POINT THE SYSTEM
 WILL TRANSITION TO SCH 40 METAL PIPING @ .5LB. PROVIDE
 ANY AND ALL SIZING TABLES NEEDED TO PROPERLY SIZE THIS
 SYSTEM. SUBMIT TWO COPIES OF ALL APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
  
 7) NEW COMMENT: IF 2LB SYSTEM. SHOW THE LOCATION OF ALL
 MP (STEP-DOWN) REGULATORS. A LISTED SHUTOFF VALVE SHALL
 BE INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 2017 FBC-FUEL GAS SEC.409.4, FBC-RESIDENTIAL SEC. G
 2420.4.
  
 8) NEW COMMENT: IF 2LB SYSTEM. SHOW THE DISTANCE FROM
 THE 2 PSI REGULATOR TO THE APPLIANCE. COMPLY WITH 2017
 FBC-FUEL GAS SEC. 402.4.1 OR 2017 FBC-RES. SEC.
 G2413.4.1, G2413.4.2 FOR THE PROPER PIPE SIZE AND BTU
 LOAD.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  