2019-03-27 17:33:51 | GAS 1ST REVIEW**DENIED** |
| |
| 1) SHOW WHERE YOU ARE CONNECTING INTO THE EXISTING |
| SYSTEM. PROVIDE PIPE MATERIAL AND SIZE. SUBMIT AN |
| ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL |
| CUT SECTIONS OF PIPE PER 2017 FBC-FUEL GAS, SECS. |
| 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1, |
| G2413.4.2. |
| |
| 2) CITY RECORDS (PERMIT # 02100505) LIST OTHER GAS |
| FIXTURES IN HOME. LIST THE BTU LOAD OF EACH APPLIANCE |
| AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 |
| FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4 |
| AND TABLES G2413.4 (1 ) THROUGH G2413.4 THE PLANS |
| INDICATE AN EXISTING GAS METER. THE BTU LOAD OF THE |
| EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU |
| LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS |
| PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST |
| BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A |
| GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF |
| EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE |
| PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, |
| G2413.2, G2413.3. |
| |
| 3) CITY RECORDS SHOW THIS SYSTEM AS 12" W.C AND NOT 2 |
| LB AS YOU CALL OUT. PLEASE CLARIFY. IS IT YOUR INTENT |
| TO INSTALL PRESSURE REG'S AT ALL FIXTURES? INDICATE THE |
| DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN PER |
| 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 THRU 402.6 OR 2017 |
| FBC RES. SEC. G2413.2, G2413.4.3. |
| |
| 4) PROVIDE A COMPLETE AND ACCURATE GAS ISOMETRIC |
| DRAWING. FBC 107.3.5 |
| |