Plan Review Notes
Plan Review Notes For Permit 19030800
Permit Number 19030800
Review Stop G
Sequence Number 1
Notes
Date Text
2019-03-27 17:33:51GAS 1ST REVIEW**DENIED**
  
 1) SHOW WHERE YOU ARE CONNECTING INTO THE EXISTING
 SYSTEM. PROVIDE PIPE MATERIAL AND SIZE. SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2017 FBC-FUEL GAS, SECS.
 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1,
 G2413.4.2.
  
 2) CITY RECORDS (PERMIT # 02100505) LIST OTHER GAS
 FIXTURES IN HOME. LIST THE BTU LOAD OF EACH APPLIANCE
 AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 THE PLANS
 INDICATE AN EXISTING GAS METER. THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 3) CITY RECORDS SHOW THIS SYSTEM AS 12" W.C AND NOT 2
 LB AS YOU CALL OUT. PLEASE CLARIFY. IS IT YOUR INTENT
 TO INSTALL PRESSURE REG'S AT ALL FIXTURES? INDICATE THE
 DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN PER
 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 THRU 402.6 OR 2017
 FBC RES. SEC. G2413.2, G2413.4.3.
  
 4) PROVIDE A COMPLETE AND ACCURATE GAS ISOMETRIC
 DRAWING. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 THUNT@CGA SOLUTIONS.COM
  