Plan Review Notes
Plan Review Notes For Permit 19030794
Permit Number 19030794
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-05 15:07:06PLUMBING 1ST REVIEW**DENIED**
  
 1) PLUMBING FLAT DRAWING AND PLUMBING ISOMETRIC DON'T
 MATCH. FBC 107.3.5
  
 2) SHOWER IS NOT PERMITTED TO BE WET VENTED BY THE
 WASHING MACHINE AND IT APPEARS FROM THE PLAN
 MEARSUREMENTS THE DISTANCE FROM THE POINT OF VENT TO
 THE P-TRAP IS OVER 8' FBC -P 909.1. ALSO THE WASHING
 MACHINE IS NOT PERMITTED TO DISCHARGE INTO THE BATHROOM
 GROUP WET VENT AS SHOWN OF THE ISOMETRIC. FBC-P 912.1
  
 3) THE OLD PLAN SHOWED A TANKLESS IS THE WATER HEATER
 AT THE NEW LOCATION TANKLESS? IF THE WATER IS STORAGE
 TYPE PROVIDE PAN DETAIL SHOWING HOW THE PAN DRAIN IS
 GOING TO DISCHARGE TO THE OUTSIDE AND TERMINATED NOT
 LESS THAN 6" FROM THE GROUND SURFACE. FBC-P 504.7.2.
 THE ACCES SHOULD TO THE WATER HEATER MUST BE LARGE
 ENOUGH TO ALLOW SERVICE AND REPLACEMENT OF THE WATER
 HEATER. 502.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]