2019-03-26 08:39:40 | W.P.B. PERMIT: 19030777 | | REVIEWED: MARCH 26, 2019 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER PX4191 | | [email protected] | | 561-805-6718 | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC[B] = FBC BUILDING | | | | 107.3.5 FBC[AMENDED] | | THIS IS A GENERAL COMMENT AND I?M JUST LOOKING FOR | | CONFIMATION FROM ENGINEER OF RECORD THAT ALL CONDITIONS | | HAVE BEEN CONSIDERED. | | THE ENGINEERING SUBMITTAL STATES THAT WIRE CAN DEFLECT | | FROM 11.51 INCHES TO 16.91 INCHES. | | IT APPEARS IN PLAN THAT THE WIRES ARE PLACED WITHIN | | THOSE DISTANCES STATED ABOVE TO THE DECORATIVE | | SCREENING. | | PLEASE VERIFY THAT DISTANCES ARE ADEQUATE AND ALSO | | VERIFY THAT SCREENING PANELS WOULD NOT DETACH. | | I THINK THAT IT WOULD BE A MAINTENANCE FUNCTION IF | | SREENING WAS DAMAGED, BUT HAVING REVIEWED BOTH VEHICLE | | BARRIER AND DECORATIVE SCREENING PANELS I WANTED TO | | MAKE SURE THE INTERACTION BETWEEN THE TWO IS FACTORED | | IN. | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | [email protected] | | | | | | |
|