Plan Review Notes For Permit 19030768 |
Permit Number |
19030768 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-04-03 10:35:10 | FAILED | | | | PROVIDE WRITTEN RESPONSE TO COMMENTS. | | | | 1) THIS PERMIT IS LISTED AS A REVISION TO MASTER PERMIT | | 18101337; HOWEVER, THE CIVIL SHEETS INCLUDED WITH THE | | SUBMITTAL WERE NOT APPROVED AS PART OF PERMIT 18101337. | | PLEASE IDENTIFY THE PERMIT THAT APPROVED THE CIVIL | | PLANS AND PROVIDE THE PERMIT NUMBER(S) AND VERIFY WITH | | THE BUILDING DIVISION STAFF THAT THE REVISION TO THE | | CIVIL PLANS CAN BE INCLUDED WITH THIS REVISION, OR IF | | IT REQUIRES A SEPARATE SUBMITTAL. | | | | 2) THE PROPOSED NEW FIRE SERVICE AND WATER SERVICE | | LINES APPEAR TO BE IN DIRECT CONFLICT WITH TWO REQUIRED | | PALMS. PROVIDE A PLAN SHOWING THE LINES AND THE PALMS | | WITH ADEQUATE SEPARATION FROM THE PROPOSED AND EXISTING | | UTILITIES IN THE AREA. COORDINATE WITH YOUR THE | | LANDSCAPE ARCHITECT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | [email protected] | | |
|