Date |
Text |
2019-05-07 16:00:29 | PLUMBING 2ND REVIEW**DENIED** PLEASE NOTE FL ST 553.80 |
| (B)2B WITH RESPECT TO EVALUATION OF DESIGN |
| PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS |
| IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE |
| FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| REVIEW. |
| |
| 1) ANSWERED |
| |
| 2) NOT ADDRESSED: YOU PROVIDED A PARALLEL APPROACH BUT |
| DID NOT CENTER THE FIXTURE ON THE CLEAR FLOOR SPACE. |
| SHT A3.0 WAS NOT REVISED AND IS STILL SHOWING CABINET |
| HEIGHT AS 3'0". COMMENT: BOTH THE EXAM ROOM AND PRETEST |
| SINK SHALL COMPLY WITH FBC-A 212.3 AS AT LEAST 1 OF |
| EACH TYPE SHALL BE PROVIDED IN EACH ACCESSIBLE ROOM. |
| PROVIDE CLEAR FLOOR SPACE, TURNING SPACE, AND COUNTER |
| TOP HEIGHT OF 34" ON PLAN. FBC-A 606 |
| |
| 3) ANSWERED |
| |
| 4) ANSWERED |
| |
| TIM HUNT |
| PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| CITY OF WEST PALM BEACH |
| 561-248-2703 |
| [email protected] |
| [email protected] |
| |