Plan Review Notes For Permit 19030753 |
Permit Number |
19030753 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-05-15 10:30:27 | THE FOLLOWING COMMENTS WERE SUBMITTED BY SANDRA THOMAS, | | FIRE INVESTIGATOR, BUREAU OF FIRE PREVENTION, WEST PALM | | BEACH FIRE RESCUE. | | | | 1. COVER PAGE SUGGESTS BUILDING IS UNSPRINKLERED, WHILE | | PAGE FP-100 ILLUSTRATES SPRINKLERS TO BE INSTALLED. | | | | 2. 1 HR. DEMISING WALL ON PAGE G-003 IS BASED ON HAVING | | A SPRINKLERED BUILDING, WHICH AGAIN CONTRADICTS WHAT IS | | DEPICTED ON PAGE FP-100. | | | | 3. PAGE E-200 NOTES # 32 & 35 SUGGEST A FIRE ALARM | | SYSTEM TO BE INSTALLED. CLARIFICATION IS NEEDED. | | | | WHERE APPLICABLE: | | | | ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A CERTIFIED | | FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA 72. A | | SEPARATE SHOP DRAWING IS REQUIRED TO BE SUBMITTED, | | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU | | PRIOR TO ANY WORK ON THE SYSTEM. | | | | ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE | | COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND | | SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE | | REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE | | FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM. | | | | S. THOMAS | | 561-804-4728 |
|