2019-04-10 15:27:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19030753
 4/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.0: REFER TO SECTION 510.1 FBC M AND
 DESCRIBE THE ACTIVITIES AND PROCESSES THAT TAKE PLACE
 IN THE LAB AND WHAT MATERIALS OR CHEMICALS ARE USED AND
 STORED THERE. IF THIS ROOM IS CLASSIFED AS A LAB THEN
 AN EXHAUST VENTILATION SYSTEM IS REQUIRED, AND
 RECIRCULATION OF AIR FROM THE ROOM IS PROHIBITED- TABLE
 403.3.1.1 FBC M. PLEASE PROVIDE EXPALNATORY NOTES ON
 THE PLAN TO CLARIY. IF THIS ROOM IS NOT A LAB, PLEASE
 CHANGE THE NAME.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  