Plan Review Notes For Permit 19030752 |
Permit Number |
19030752 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-03-18 16:27:41 | PLUMBING 1ST REVIEW**DENIED** | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | YOU HAVE NOT INCLUDED ANY SUPPORTING DOCUMENTS OTHER | | THEN A SIGNED CONTRACT. | | | | 1) PROVIDE A COMPLETE FLOOR PLAN SHOWING EACH FIXTURE | | IN THE HOME AND WHAT FIXTURES YOU WE BE REPIPING. ALSO | | NOTE DISTANCE TO EACH FIXTURE. FBC 107.3.5 | | | | 2) NOTE ON PLAN ALL NEW PIPING WILL REQUIRED INSULATION | | MIN R-3 IN THE FOLLOWING LOCATIONS OR USE.**R403.5.3HOT | | WATER PIPE INSULATION** | | INSULATION FOR HOT WATER PIPE WITH A MINIMUM THERMAL | | RESISTANCE (R-VALUE) OF R-3 SHALL BE APPLIED TO THE | | FOLLOWING: | | | | 1.PIPING 3/4 INCH (19.1 MM) AND LARGER IN NOMINAL | | DIAMETER. | | | | 2.PIPING SERVING MORE THAN ONE DWELLING UNIT. | | | | 3.PIPING LOCATED OUTSIDE THE CONDITIONED SPACE. | | | | 4.PIPING FROM THE WATER HEATER TO A DISTRIBUTION | | MANIFOLD. | | | | 5.PIPING LOCATED UNDER A FLOOR SLAB. | | | | 6.BURIED IN PIPING. | | | | 7.SUPPLY AND RETURN PIPING IN RECIRCULATION SYSTEMS | | OTHER THAN DEMAND RECIRCULATION SYSTEMS. | | | | | | TIM HUNT | | PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | | | |
|