Plan Review Notes
Plan Review Notes For Permit 19030752
Permit Number 19030752
Review Stop P
Sequence Number 1
Notes
Date Text
2019-03-18 16:27:41PLUMBING 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 YOU HAVE NOT INCLUDED ANY SUPPORTING DOCUMENTS OTHER
 THEN A SIGNED CONTRACT.
  
 1) PROVIDE A COMPLETE FLOOR PLAN SHOWING EACH FIXTURE
 IN THE HOME AND WHAT FIXTURES YOU WE BE REPIPING. ALSO
 NOTE DISTANCE TO EACH FIXTURE. FBC 107.3.5
  
 2) NOTE ON PLAN ALL NEW PIPING WILL REQUIRED INSULATION
 MIN R-3 IN THE FOLLOWING LOCATIONS OR USE.**R403.5.3HOT
 WATER PIPE INSULATION**
 INSULATION FOR HOT WATER PIPE WITH A MINIMUM THERMAL
 RESISTANCE (R-VALUE) OF R-3 SHALL BE APPLIED TO THE
 FOLLOWING:
  
 1.PIPING 3/4 INCH (19.1 MM) AND LARGER IN NOMINAL
 DIAMETER.
  
 2.PIPING SERVING MORE THAN ONE DWELLING UNIT.
  
 3.PIPING LOCATED OUTSIDE THE CONDITIONED SPACE.
  
 4.PIPING FROM THE WATER HEATER TO A DISTRIBUTION
 MANIFOLD.
  
 5.PIPING LOCATED UNDER A FLOOR SLAB.
  
 6.BURIED IN PIPING.
  
 7.SUPPLY AND RETURN PIPING IN RECIRCULATION SYSTEMS
 OTHER THAN DEMAND RECIRCULATION SYSTEMS.
  
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  